- Series name
- RXG series
- Local signalling
- Flag
- Local signalling
- Flag
- status LED
- With
- Minimum switching capacity
- 500 mW at 100 mA, 5 V DC
- Maximum switching capacity
- 2500 VA
- Maximum switching capacity
- 2500 VA
- Safety reliability data
- B10d = 100000
- Operating rate
- <= 1800 cycles/hour under load · <= 18000 cycles/hour no-load
- Utilisation coefficient
- 20 %
- Utilisation coefficient
- 20 %
- Operating time
- 20 ms
- Reset time
- 20 ms
- Reset time
- 20 ms
- Dielectric strength
- 1000 V AC between contacts with micro disconnection · 5000 V AC between coil and contact with reinforced insulation · 1300 V AC terminals and case with basic insulation
- Dielectric strength
- 1000 V AC between contacts with micro disconnection · 5000 V AC between coil and contact with reinforced insulation · 1300 V AC terminals and case with basic insulation
- Protection category
- RT I
- Pollution degree
- 2
- Test levels
- Level A group mounting
- Shape of pin
- Flat (faston type)
- IP degree of protection
- IP40
- Control type
- Lockable test button