Schneider Electric Acti9 iC60 RCBO residual current breaker with overcurrent protection (rcbo), rated 10 A. Residual current breaker with overcurrent protection (RCBO), Acti9 iC60H3, 3P+Ns, C Curve, 10A, 30mA, A type, 10000A.
Brand
Schneider Electric
Range / Series
Acti9
Rated current
10 A
Poles
3P
IP rating
IP20
Weight
1 kg
Complete product informationProduct description and supplied technical information
Residual current breaker with overcurrent protection (RCBO), Acti9 iC60H3, 3P+Ns, C Curve, 10A, 30mA, A type, 10000A. Genuine Schneider Electric product supplied by United Force.
Technical specifications
Circuit breaker application
Distribution
Range
Acti9
Product name
Acti9 iC60 RCBO
Product or component type
Residual current breaker with overcurrent protection (RCBO)
Device short name
iC60H3 RCBO
Poles description
3P + Ns
[In] rated current
10 A at 30 °C
Earthing system
TN
Curve code
C
Earth-leakage sensitivity
30 mA
Breaking capacity
10000 A Icn at 400/415 V
Neutral position
Left
Number of protected poles
3
Device location in system
Outgoer
Network frequency
50/60 Hz
Network type
AC
Trip unit technology
Thermal-magnetic
[Ue] rated operational voltage
400/415 V
Residual current tripping technology
Voltage dependent
Earth-leakage protection time delay
Instantaneous
Earth-leakage protection class
Type A
[Icw] rated short-time withstand current
Icw: 250 A during 8/20 µs impulse withstand
[Ics] rated service breaking capacity
7500 A
Limitation class
3
[Ui] rated insulation voltage
500 V
[Uimp] rated impulse withstand voltage
4 kV
Surge current
250 A
Suitability for isolation
Yes conforming to IEC 61009-1
Control type
Toggle
Local signalling
ON/OFF indication
Mounting mode
Clip-on
Mounting support
DIN rail · Chassis
Comb busbar and distribution block compatibility
YES
9 mm pitches
6
Height
112 mm
Width
54 mm
Depth
77.2 mm
Product weight
462 g
Colour
White
Mechanical durability
20000 cycles
Electrical durability
5000 cycles
Provision for padlocking
Padlockable with padlock Ø 4 mm · Lead seal
Locking options description
ON/OFF locking facilities
Connections - terminals
Screw clamp terminal (top) 1…25 mm² rigid without cable end · Screw clamp terminal (top) 1…16 mm² flexible
Wire stripping length
Power circuit: 11 mm for bottom connection · Power circuit: 14 mm for top connection