Schneider Electric Acti9 iC60 miniature circuit-breaker, rated 2 A. Miniature circuit breaker (MCB), Acti9 iC60L, 2P, 2A, C curve, 15000A (IEC/EN 60898-1), 100kA (IEC/EN 60947-2).
Miniature circuit breaker (MCB), Acti9 iC60L, 2P, 2A, C curve, 15000A (IEC/EN 60898-1), 100kA (IEC/EN 60947-2). Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | Acti9 |
|---|
| Product name | Acti9 iC60 |
|---|
| Product or component type | Miniature circuit-breaker |
|---|
| Device short name | iC60L |
|---|
| Device application | Distribution |
|---|
| Poles description | 2P |
|---|
| Number of protected poles | 2 |
|---|
| [In] rated current | 2 A |
|---|
| Network type | DC · AC |
|---|
| Trip unit technology | Thermal-magnetic |
|---|
| Curve code | C |
|---|
| Utilisation category | Category A conforming to EN/IEC 60947-2 |
|---|
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 · Yes conforming to EN/IEC 60898-1 |
|---|
| Standards | EN/IEC 60947-2 · EN/IEC 60898-1 |
|---|
| Network frequency | 50/60 Hz |
|---|
| [Ue] rated operational voltage | 12...133 V AC 50/60 Hz · 220...240 V AC 50/60 Hz · 380...415 V AC 50/60 Hz · 440 V AC 50/60 Hz · <= 125 V DC |
|---|
| Magnetic tripping limit | 8 x In +/- 20 % |
|---|
| Breaking capacity | 100 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 · 100 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 · 100 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 · 70 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 · 20 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 · 15000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
|---|
| [Ics] rated service breaking capacity | 100 kA 100 % x Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 · 100 kA 100 % x Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 · 100 kA 100 % x Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 · 70 kA 100 % x Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 · 20 kA 100 % x Icu at <= 125 V DC conforming to EN/IEC 60947-2 |
|---|
| Limitation class | 3 conforming to EN/IEC 60898-1 |
|---|
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|---|
| [Uimp] rated impulse withstand voltage | 6 kV conforming to EN/IEC 60947-2 |
|---|
| Contact position indicator | Yes |
|---|
| Control type | Toggle |
|---|
| Local signalling | Trip indicator |
|---|
| Mounting mode | Clip-on · Removable comb busbar installed |
|---|
| Mounting support | 35 mm DIN rail |
|---|
| Comb busbar and distribution block compatibility | Top or bottom: YES |
|---|
| Connection pitch | 18 mm between phases |
|---|
| 9 mm pitches | 4 |
|---|
| Height | 85 mm |
|---|
| Width | 36 mm |
|---|
| Depth | 78.5 mm |
|---|
| Product weight | 0.25 kg |
|---|
| Colour | White |
|---|
| Mechanical durability | 20000 cycles |
|---|
| Electrical durability | 10000 cycles |
|---|
| Connections - terminals | Single terminal (top or bottom) , for 1 cable(s) , 1…25 mm², rigid, copper · Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible, copper · Single terminal (top or bottom) , for 1 cable(s) , 1…16 mm², flexible with ferrule, copper · Single terminal (top or bottom) , for 1.0 cable(s) , flexible, copper or aluminium, with ring terminal and accessory |
|---|
| Wire stripping length | 14 mm for top or bottom connection |
|---|
| Tightening torque | 2 N.m top or bottom |
|---|
| Earth-leakage protection | Separate block |
|---|
| IP degree of protection | IP20 conforming to IEC 60529 · IP40 in modular enclosure (Insulation class II) conforming to IEC 60529 |
|---|
| Pollution degree | 3 conforming to EN/IEC 60947-2 |
|---|
| Overvoltage category | IV |
|---|
| Tropicalisation | 2 conforming to IEC 60068-1 |
|---|