Schneider Electric analog input module kit. Analog Input Module + Base, 8 In, Current, 1/2 wires, Loop Power, Modicon Edge I/O NTS.
Analog Input Module + Base, 8 In, Current, 1/2 wires, Loop Power, Modicon Edge I/O NTS. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range of product | Modicon Edge I/O NTS |
|---|
| Product or component type | Analog input module kit |
|---|
| Kit composition | NTSACI0802X module · NTSXBA0200H base |
|---|
| Mandatory accessory | NTSXTB18_0_H terminal block |
|---|
| Product compatibility | NTSN..... |
|---|
| Range compatibility | Logic/motion controller - Modicon M262 · Modicon M580 · Third party |
|---|
| Device application | Industrial application |
|---|
| Analogue input number | 8 |
|---|
| Operating mode | Isochronous/Asynchronous |
|---|
| Analogue input type | Current +/- 20 mA · Current 0...20 mA · Current 4...20 mA |
|---|
| Input wiring mode | 1 or 2 wires |
|---|
| Analogue input resolution | 15 bits + sign |
|---|
| Permitted overload on inputs | 30 V at 50 mA maximum current |
|---|
| Input impedance | 250 Ohm + internal current protector 10 Ohm typical |
|---|
| Sampling duration | 1.595 ms per module |
|---|
| Input protection type | Over current / miswiring protection per channel for current input |
|---|
| Sensor power supply protection | Over current protection per channel · Short circuit protection on loop power supply per channel |
|---|
| Input diagnostic | Underflow error per channel · Overflow error per channel · Broken wire error per channel · Hardware error per channel · Calibration error per channel · Loop power supply error per channel |
|---|
| LSB value | 0.61 µA, +/-20 mA · 0.61 µA, 0...20 mA · 0.49 µA, 4...20 mA |
|---|
| Type of cable | Shielded cable |
|---|
| Temperature drift | ± 0.004 % FS/ °C |
|---|
| Measurement error | <= 0.1 % FS 25 °C · <= 0.3 % FS - 20…60 °C |
|---|
| Non-linearity | <= 0.01 % FS, analogue input type: voltage/current |
|---|
| Common mode rejection | 90 dB |
|---|
| Sensor power supply | 19.2…30 V DC Loop power |
|---|
| Power supply type | Bus power from power supply bus (24 Vdc) · Field power from power supply field (24 Vdc) |
|---|
| Rated operational voltage limits | 20.4...28.8 V DC |
|---|
| Typical current consumption | 36 mA at 24 V DC on the Bus current · 24 mA at 24 V DC on the internal field current minimum · 208.8 mA at 24 V DC on the internal field current maximum |
|---|
| Power dissipation in W | 2.3 W maximum at 24 V DC |
|---|
| Maximum cable distance between devices | Shielded cable: <1000 m for current input |
|---|
| Isolation between channels and bus | 1500 V AC |
|---|
| Isolation between channels and field pwr | No |
|---|
| Isolation between field power and bus | 1500 V AC |
|---|
| Hot swapping fallback | Yes |
|---|
| Local signalling | 1 LED green for module operating (RUN) · 1 LED per channel green for channel diagnostic · 1 LED red for module error (ERR) |
|---|
| Housing colour | Grey |
|---|
| Mounting support | Top hat type TH35-7.5 rail conforming to IEC 60715 · Top hat type TH35-15 rail conforming to IEC 60715 |
|---|
| Height | 121 mm |
|---|
| Width | 30 mm |
|---|
| Depth | 80 mm |
|---|
| Product weight | 0.131 kg |
|---|
| IP degree of protection | IP20 |
|---|
| Marking | CE · UKCA · CULus · RCM |
|---|
| Product certifications | CE · UKCA · CULus · RCM · Merchant Navy - EU RO MR (pending) · EAC (pending) · ATEX Zone 2 (pending) · IECEx zone 2 (pending) · CCC Ex zone 2 (pending) |
|---|
| Standards | EN/IEC 61131-2 · EN 61010-2-201 · UL 61010-2-201 · IACS E10 · EN/IEC 61000-6-5 · EN/IEC 61850-3 · EN/IEC 60079-0 · EN 50155 · EN 50121-4 · EN 50121-5 |
|---|