Schneider Electric standard analog input kit. analog input kit, Modicon STB, standard, 4-20mA, 4 I, 15bits with sign.
analog input kit, Modicon STB, standard, 4-20mA, 4 I, 15bits with sign. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range of product | Modicon STB distributed I/O solution |
|---|
| Product or component type | Standard analog input kit |
|---|
| Kit composition | STBACI8320 module · STBXBA2000 base · STBXTS1100, 6-terminal screw type connector · STBXTS2100, 6-terminal spring clamp connector |
|---|
| Product compatibility | Power distribution module STBPDT3100/3105 · Mounting base STBXBA2000 |
|---|
| Analogue input number | 4 |
|---|
| Type of filter | Single low pass input filter 985 Hz |
|---|
| Analogue output number | 0 |
|---|
| Absolute maximum input | 25 mA/50 V |
|---|
| Cold swapping | Yes |
|---|
| Data format | IEC 61131-2 · EN 61131-2 |
|---|
| Update time | 80 ms |
|---|
| Integral linearity | +/- 0.05 %FS |
|---|
| Differential linearity | Monotonic |
|---|
| Maximum supply current for sensors | 25 mA per input channels |
|---|
| Absolute accuracy error | +/- 0.4 % of full scale 25 °C |
|---|
| Addressing requirement | 8 input words |
|---|
| Supply | Power distribution module |
|---|
| Analogue input type | Current 0...20 mA · Current 4...20 mA |
|---|
| Analogue input resolution | 15 bits + sign |
|---|
| Input impedance | 250 Ohm |
|---|
| Input protection type | Protected against short-circuit |
|---|
| Temperature drift | +/-0.005 %/°C |
|---|
| Typical current consumption | 95 mA at 5 V DC for logic bus |
|---|
| Isolation between channels and bus | 1780 Vrms for 1 minute |
|---|
| Hot swapping fallback | Yes for standard NIMs |
|---|
| Local signalling | 1 LED green for module status (RDY) · 1 LED red for module error (ERR) |
|---|
| Height | 18.4 mm |
|---|
| Width | 128.3 mm |
|---|
| Depth | 70 mm |
|---|
| Overvoltage category | II |
|---|
| IP degree of protection | IP20 |
|---|
| Marking | CE |
|---|
| Product certifications | CSA · C-Tick · ATEX Cat 3G · FM Class 1 Division 2 · UL |
|---|
| Ambient air temperature for operation | -25…70 °C (without derating) |
|---|
| Ambient air temperature for storage | -40…85 °C without derating |
|---|
| Relative humidity | 95 % at 60 °C without condensation |
|---|
| Operating altitude | 2000 m |
|---|
| Pollution degree | 2 |
|---|
| Vibration resistance | +/-0.35 mm (f = 10…58 Hz) · 3 gn (f = 58…150 Hz) on 35 mm DIN rail · 5 gn (f = 58…150 Hz) on 35 mm DIN rail |
|---|
| Shock resistance | 30 gn for 11 ms conforming to IEC 88 reference 2-27 |
|---|
| Unit Type of Package 2 | S02 |
|---|
| Number of Units in Package 2 | 28 |
|---|
| Package 2 Height | 15.0 cm |
|---|
| Package 2 Width | 30.0 cm |
|---|
| Package 2 Length | 40.0 cm |
|---|