- Product or component type
- Variable speed drive
- Product specific application
- Complex machines
- Product specific application
- Complex machines
- Format of the drive
- Book
- Option card
- Communication module, CANopen · Communication module, EtherCAT · Communication module, Profibus DP V1 · Communication module, PROFINET · Communication module, Ethernet Powerlink · Communication module, EtherNet/IP · Communication module, DeviceNet
- EMC filter
- Class C2 EMC filter integrated
- Discrete input number
- 7
- Discrete input number
- 7
- Discrete input logic
- Positive logic (source) · Negative logic (sink)
- Discrete output number
- 3
- Discrete output type
- Open collector DQ+ 0…1 kHz 30 V DC 100 mA · Open collector DQ- 0…1 kHz 30 V DC 100 mA
- Discrete output type
- Open collector DQ+ 0…1 kHz 30 V DC 100 mA · Open collector DQ- 0…1 kHz 30 V DC 100 mA
- Analogue output number
- 1
- Analogue output type
- Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10 bits · Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bits
- Relay output type
- Configurable relay logic R1A 1 NO electrical durability 100000 cycles · Configurable relay logic R1B 1 NC electrical durability 100000 cycles · Configurable relay logic R1C · Configurable relay logic R2A 1 NO electrical durability 100000 cycles · Configurable relay logic R2C
- Method of access
- Slave CANopen
- Asynchronous motor control profile
- Voltage/frequency ratio, 5 points · Flux vector control without sensor, standard · Voltage/frequency ratio - Energy Saving, quadratic U/f · Flux vector control without sensor - Energy Saving · Voltage/frequency ratio, 2 points
- Asynchronous motor control profile
- Voltage/frequency ratio, 5 points · Flux vector control without sensor, standard · Voltage/frequency ratio - Energy Saving, quadratic U/f · Flux vector control without sensor - Energy Saving · Voltage/frequency ratio, 2 points
- Synchronous motor control profile
- Vector control without sensor
- Acceleration and deceleration ramps
- Linear · U · S · CUS · Ramp switching · Acceleration/deceleration ramp adaptation · Acceleration/deceleration automatic stop with DC injection
- Motor slip compensation
- Automatic whatever the load · Adjustable 0...300 % · Not available in voltage/frequency ratio (2 or 5 points)
- Braking to standstill
- By DC injection
- Brake chopper integrated
- True
- Prospective line Isc
- 5 kA