- Range of product
- Altivar Machine ATV320
- Product or component type
- Variable speed drive
- Product specific application
- Complex machines
- Product specific application
- Complex machines
- Product specific application
- Complex machines
- Format of the drive
- Book
- Communication port protocol
- Modbus serial · CANopen
- Option card
- Communication module, CANopen · Communication module, EtherCAT · Communication module, Profibus DP V1 · Communication module, PROFINET · Communication module, Ethernet Powerlink · Communication module, EtherNet/IP · Communication module, DeviceNet
- Option card
- Communication module, CANopen · Communication module, EtherCAT · Communication module, Profibus DP V1 · Communication module, PROFINET · Communication module, Ethernet Powerlink · Communication module, EtherNet/IP · Communication module, DeviceNet
- EMC filter
- Class C3 EMC filter integrated
- IP degree of protection
- IP20
- Discrete input number
- 7
- Discrete input logic
- Positive logic (source) · Negative logic (sink)
- Discrete output number
- 3
- Analogue input number
- 3
- Analogue input type
- AI1 voltage: 0...10 V DC, impedance: 30 kOhm, resolution 10 bits · AI2 bipolar differential voltage: +/- 10 V DC, impedance: 30 kOhm, resolution 10 bits · AI3 current: 0...20 mA (or 4-20 mA, x-20 mA, 20-x mA or other patterns by configuration), impedance: 250 Ohm, resolution 10 bits
- Analogue output type
- Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10 bits · Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bits
- Analogue output type
- Software-configurable current AQ1: 0...20 mA impedance 800 Ohm, resolution 10 bits · Software-configurable voltage AQ1: 0...10 V DC impedance 470 Ohm, resolution 10 bits
- Relay output type
- Configurable relay logic R1A 1 NO electrical durability 100000 cycles · Configurable relay logic R1B 1 NC electrical durability 100000 cycles · Configurable relay logic R1C · Configurable relay logic R2A 1 NO electrical durability 100000 cycles · Configurable relay logic R2C
- 4 quadrant operation possible
- True
- 4 quadrant operation possible
- True
- Synchronous motor control profile
- Vector control without sensor
- Acceleration and deceleration ramps
- Linear · U · S · CUS · Ramp switching · Acceleration/deceleration ramp adaptation · Acceleration/deceleration automatic stop with DC injection
- Motor slip compensation
- Automatic whatever the load · Adjustable 0...300 % · Not available in voltage/frequency ratio (2 or 5 points)
- Braking to standstill
- By DC injection
- Brake chopper integrated
- True
- Prospective line Isc