| Range of product | Easy Altivar 610 |
|---|
| Product specific application | Fan, pump, compressor, conveyor |
|---|
| Product or component type | Variable speed drive |
|---|
| Device short name | ATV610 |
|---|
| Variant | Standard version |
|---|
| Product destination | Asynchronous motors · Synchronous motors |
|---|
| Mounting mode | Cabinet mount |
|---|
| EMC filter | Integrated conforming to IEC 61800-3 category C3 with 50 m |
|---|
| IP degree of protection | IP20 |
|---|
| Type of cooling | Forced convection |
|---|
| Supply frequency | 50...60 Hz +/-5 % |
|---|
| Network number of phases | 3 phases |
|---|
| [Us] rated supply voltage | 380...460 V - 15...10 % |
|---|
| Motor power kW | 110 kW for normal duty · 90 kW for heavy duty |
|---|
| Motor power hp | 150 hp for normal duty · 125 hp for heavy duty |
|---|
| Line current | 201 A at 380 V (normal duty) · 175.7 A at 460 V (normal duty) · 170 A at 380 V (heavy duty) · 149.1 A at 460 V (heavy duty) |
|---|
| Prospective line Isc | 50 kA |
|---|
| Apparent power | 140.0 kVA at 460 V (normal duty) · 118.8 kVA at 460 V (heavy duty) |
|---|
| Continuous output current | 211 A at 2.5 kHz for normal duty · 173 A at 2.5 kHz for heavy duty |
|---|
| Maximum transient current | 232 A during 60 s (normal duty) · 260 A during 60 s (heavy duty) |
|---|
| Asynchronous motor control profile | Variable torque standard · Optimized torque mode · Constant torque standard |
|---|
| Output frequency | 0.1…500 Hz |
|---|
| Nominal switching frequency | 2.5 kHz |
|---|
| Switching frequency | 1...8 kHz adjustable |
|---|
| number of preset speeds | 16 preset speeds |
|---|
| Communication port protocol | Modbus serial |
|---|
| Option card | Slot A: communication card, Profibus DP V1 · Slot A: digital or analog I/O extension card · Slot A: relay output card |
|---|
| Output voltage | <= power supply voltage |
|---|
| Motor slip compensation | Can be suppressed · Adjustable · Not available in permanent magnet motor law · Automatic whatever the load |
|---|
| Acceleration and deceleration ramps | Linear adjustable separately from 0.01 to 9000 s · S, U or customized |
|---|
| Braking to standstill | By DC injection |
|---|
| Protection type | Thermal protection: motor · Motor phase break: motor · Thermal protection: drive · Overheating: drive · Overcurrent between output phases and earth: drive · Overload of output voltage: drive · Short-circuit protection: drive · Motor phase break: drive · Overvoltages on the DC bus: drive · Line supply overvoltage: drive · Line supply undervoltage: drive · Line supply phase loss: drive · Overspeed: drive · Break on the control circuit: drive |
|---|
| Frequency resolution | Display unit: 0.1 Hz · Analog input: 0.012/50 Hz |
|---|
| Electrical connection | Control, screw terminal: 0.5...1.5 mm² · Line side, screw terminal: 2 x 50...3 x 120 mm² · Motor, screw terminal: 3 x 50...3 x 120 mm² |
|---|
| Connector type | 1 RJ45 (on the remote graphic terminal) for Modbus serial |
|---|
| Physical interface | 2-wire RS 485 for Modbus serial |
|---|
| Transmission frame | RTU for Modbus serial |
|---|
| Transmission rate | 4.8, 9.6, 19.2, 38.4 kbit/s for Modbus serial |
|---|
| Type of polarization | No impedance for Modbus serial |
|---|
| Number of addresses | 1…247 for Modbus serial |
|---|
| Method of access | Slave |
|---|
| Supply | External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short-circuit protection · Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection |
|---|
| Local signalling | 2 LEDs for local diagnostic · 1 LED (yellow) for embedded communication status · 2 LEDs (dual colour) for communication module status · 1 LED (red) for presence of voltage |
|---|
| Width | 300 mm |
|---|
| Depth | 375 mm |
|---|