Schneider Electric TeSys auxiliary contact, rated 5 A. Auxiliary contact, TeSys GV4, 690VAC, 1 NO/NC.
Auxiliary contact, TeSys GV4, 690VAC, 1 NO/NC. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | TeSys |
|---|
| Device short name | GV4AE |
|---|
| Product or component type | Auxiliary contact |
|---|
| Device application | Signalling |
|---|
| Range compatibility | TeSys TeSys GV4 · TeSys TeSys BV4 |
|---|
| Auxiliary contact composition | 1 NO/NC |
|---|
| [Ue] rated operational voltage | <= 690 V |
|---|
| [Ith] conventional free air thermal current | 5 A conforming to IEC 60947-5-1 · 5 A conforming to CSA C22.2 No 14 · 5 A conforming to UL 508 |
|---|
| Mounting mode | Internal mounting |
|---|
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-1 |
|---|
| [Ie] rated operational current | 5 A <= 690 V AC-12 conforming to IEC 60947-5-1 · 5 A <= 48 V AC-15 conforming to IEC 60947-5-1 · 4 A 110/127 V AC-15 conforming to IEC 60947-5-1 · 3 A 220/240 V AC-15 conforming to IEC 60947-5-1 · 2.5 A 380...440 V AC-15 conforming to IEC 60947-5-1 · 0.11 A 660/690 V AC-15 conforming to IEC 60947-5-1 · 5 A <= 24 V DC-12 conforming to IEC 60947-5-1 · 2.5 A 48 V DC-12 conforming to IEC 60947-5-1 · 0.6 A 110/127 V DC-12 conforming to IEC 60947-5-1 · 0.3 A 250 V DC-12 conforming to IEC 60947-5-1 · 2.5 A <= 24 V DC-12 conforming to IEC 60947-5-1 · 1.2 A 48 V DC-12 conforming to IEC 60947-5-1 · 0.35 A 110/127 V DC-12 conforming to IEC 60947-5-1 · 0.05 A 250 V DC-12 conforming to IEC 60947-5-1 · 1 A <= 24 V DC-12 conforming to IEC 60947-5-1 · 0.2 A 48 V DC-12 conforming to IEC 60947-5-1 · 0.05 A 110/127 V DC-12 conforming to IEC 60947-5-1 · 0.03 A 250 V DC-12 conforming to IEC 60947-5-1 |
|---|
| Rated power in VA | 120 VA AC-12 at 24 V conforming to IEC 60947-5-1 · 240 VA AC-12 at 48 V conforming to IEC 60947-5-1 · 635 VA AC-12 at 110/127 V conforming to IEC 60947-5-1 · 1200 VA AC-12 at 230/240 V conforming to IEC 60947-5-1 · 2200 VA AC-12 at 380/440 V conforming to IEC 60947-5-1 · 3450 VA AC-12 at 660/690 V conforming to IEC 60947-5-1 |
|---|
| Rated power in W | DC-12: 120 W 24 V conforming to IEC 60947-5-1 · DC-12: 120 W 48 V conforming to IEC 60947-5-1 · DC-12: 66 W 110 V conforming to IEC 60947-5-1 · DC-12: 75 W 250 V conforming to IEC 60947-5-1 |
|---|
| Associated fuse rating | 5 A gG at 690 V conforming to IEC 60947-5-1 |
|---|
| Minimum switching current | 2 mA |
|---|
| Minimum switching voltage | 17 V |
|---|
| Mechanical durability | 40000 cycles |
|---|
| Connections - terminals | Spring terminals 1 0.5…1.5 mm² - cable stiffness: flexible without cable end |
|---|
| Wire stripping length | 8 mm |
|---|
| Quantity per set | Set of 1 |
|---|
| Unit Type of Package 2 | BB1 |
|---|
| Number of Units in Package 2 | 10 |
|---|
| Package 2 Height | 4.000 cm |
|---|
| Package 2 Width | 20.000 cm |
|---|
| Package 2 Length | 27.000 cm |
|---|
| Package 2 Weight | 269.000 g |
|---|
| Unit Type of Package 3 | S03 |
|---|
| Number of Units in Package 3 | 110 |
|---|
| Package 3 Height | 30.000 cm |
|---|
| Package 3 Width | 30.000 cm |
|---|
| Package 3 Length | 40.000 cm |
|---|
| Package 3 Weight | 3.455 kg |
|---|
| Warranty (in months) | 18 |
|---|