Schneider Electric complete cam switch, rated 12 A. Cam switch, Harmony K, multifixing, plastic, 1 pole, 3 steps, position 0, 45°, 12A, 45x45mm, metallic legend, marked 0 1 2 3, 35mm black handle.
Cam switch, Harmony K, multifixing, plastic, 1 pole, 3 steps, position 0, 45°, 12A, 45x45mm, metallic legend, marked 0 1 2 3, 35mm black handle. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range of product | Harmony K |
|---|
| Product or component type | Complete cam switch |
|---|
| Component name | K1 |
|---|
| [Ith] conventional free air thermal current | 12 A |
|---|
| Mounting location | Front |
|---|
| fixing mode | Multifixing |
|---|
| Cam switch head type | With front plate 45 x 45 mm |
|---|
| Type of operator | Black handle, length = 35 mm |
|---|
| Rotary handle padlocking | Without |
|---|
| Presentation of legend | With metallic legend, 0 - 1 - 2 - 3 black marking |
|---|
| Cam switch function | Stepping switch |
|---|
| Return | Without |
|---|
| Off position | With Off position |
|---|
| Poles description | 1P |
|---|
| Switching positions | Right: 0° - 45° - 90° - 135° |
|---|
| IP degree of protection | IP40 conforming to IEC 60529 |
|---|
| Number of steps | 3 |
|---|
| Switching angle | 45 ° |
|---|
| [Ui] rated insulation voltage | 690 V (pollution degree 3) conforming to IEC 60947-1 |
|---|
| [Ithe] conventional enclosed thermal current | 10 A |
|---|
| Rated operational power in W | 10500 W AC-21, 500...660 V 3 phases conforming to IEC 947-3 · 1100 W AC-3, 230 V 3 phases conforming to IEC 947-3 · 1500 W AC-23A, 230 V 3 phases conforming to IEC 947-3 · 1500 W AC-3, 400 V 1 phase conforming to IEC 947-3 · 1500 W AC-3, 400 V 3 phases conforming to IEC 947-3 · 1500 W AC-3, 500 V 3 phases conforming to IEC 947-3 · 1500 W AC-3, 690 V 3 phases conforming to IEC 947-3 · 2200 W AC-23A, 400 V 3 phases conforming to IEC 947-3 · 2200 W AC-23A, 500 V 3 phases conforming to IEC 947-3 · 2200 W AC-23A, 690 V 3 phases conforming to IEC 947-3 · 4800 W AC-21, 230 V 3 phases conforming to IEC 947-3 · 600 W AC-3, 230 V 1 phase conforming to IEC 947-3 · 8300 W AC-21, 400 V 3 phases conforming to IEC 947-3 |
|---|
| [Ie] rated operational current AC | 1.8 A at 690 V AC-3 3 phases conforming to IEC 947-3 · 2.8 A at 500 V AC-3 3 phases conforming to IEC 947-3 · 2.8 A at 690 V AC-23A 3 phases conforming to IEC 947-3 · 3.3 A at 400 V AC-3 3 phases conforming to IEC 947-3 · 3.8 A at 500 V AC-23A 3 phases conforming to IEC 947-3 · 4.6 A at 230 V AC-3 3 phases conforming to IEC 947-3 · 4.8 A at 400 V AC-23A 3 phases conforming to IEC 947-3 · 5.6 A at 230 V AC-23A 3 phases conforming to IEC 947-3 · 1 A at 500 V AC-15 conforming to IEC 947-5-1 · 2 A at 400 V AC-15 conforming to IEC 947-5-1 · 3 A at 230 V AC-15 conforming to IEC 947-5-1 |
|---|
| Electrical durability | 1000000 cycles AC-15 · 1000000 cycles AC-21 · 500000 cycles AC-23 · 500000 cycles AC-3 |
|---|
| Maximum operating rate | 2.5 cyc/mn AC-21 · 2.5 cyc/mn AC-23 · 2.5 cyc/mn AC-3 · 8.333 cyc/mn AC-15 |
|---|
| Short-circuit current | 10000 A |
|---|
| Short-circuit protection | 16 A cartridge fuse, type gG |
|---|
| [Uimp] rated impulse withstand voltage | 4 kV in isolating function · 6 kV conforming to IEC 947-1 |
|---|
| Contact operation | Slow-break |
|---|
| positive opening | With |
|---|
| Electrical connection | Captive screw clamp terminals flexible, clamping capacity: 2 x 1.5 mm² · Captive screw clamp terminals solid, clamping capacity: 1 x 2.5 mm² |
|---|
| Mechanical durability | 1000000 cycles |
|---|
| CAD overall width | 45 mm |
|---|
| CAD overall height | 45 mm |
|---|
| CAD overall depth | 87 mm |
|---|
| Product weight | 0.135 kg |
|---|
| Standards | IEC 60947-3 for power circuit · IEC 60947-5-1 for control circuit · CENELEC EN 50013 |
|---|
| Product certifications | CSA 240 V 3 hp 3 phases 2 -pole(s) · UL 240 V 0.33 hp 1 phase 2 -pole(s) · CSA 240 V 1 hp 1 phase · UL 240 V 1 hp 3 phases |
|---|
| Protective treatment | TC |
|---|
| Ambient air temperature for operation | -25…55 °C |
|---|
| Ambient air temperature for storage | -40…70 °C |
|---|
| Shock resistance | 30 gn conforming to IEC 68-2-27 |
|---|
| Vibration resistance | 5 gn conforming to IEC 68-2-6 (f = 10…150 Hz) |
|---|
| Overvoltage category | Class II conforming to IEC 536 · Class II conforming to NF C 20-030 |
|---|
| Unit Type of Package 2 | S01 |
|---|
| Number of Units in Package 2 | 10 |
|---|