Schneider Electric MasterPact MTZ2 circuit breaker, rated 1600 A. Circuit breaker frame, MasterPact MTZ2 16H1 drawout for MicroLogic X, 1600A, 66kA/415VAC (Icu), 4P right neutral.
Circuit breaker frame, MasterPact MTZ2 16H1 drawout for MicroLogic X, 1600A, 66kA/415VAC (Icu), 4P right neutral. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | MasterPacT |
|---|
| Product name | MasterPact MTZ2 |
|---|
| Device short name | MTZ2 16 H1 |
|---|
| Product or component type | Circuit breaker |
|---|
| Device application | Power distribution protection |
|---|
| Poles description | 4P |
|---|
| Neutral position | Right |
|---|
| Control type | Without control unit |
|---|
| Product compatibility | control unit MicroLogic 2.0 X · control unit MicroLogic 5.0 X · control unit MicroLogic 6.0 X · control unit MicroLogic 7.0 X · control unit MicroLogic 2.0 Xi · control unit MicroLogic 5.0 Xi · control unit MicroLogic 6.0 Xi · control unit MicroLogic 7.0 Xi |
|---|
| [In] rated current | 1600 A at 40 °C |
|---|
| Breaking capacity code | H1 66 kA 415 V AC |
|---|
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
|---|
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
|---|
| Selectivity category | Category B |
|---|
| Mounting mode | Drawout |
|---|
| Breaking capacity | 66 kA at 220/415 V AC 50/60 Hz · 66 kA at 440 V AC 50/60 Hz · 66 kA at 500/525 V AC 50/60 Hz · 66 kA at 660/690 V AC 50/60 Hz |
|---|
| [Ics] rated service breaking capacity | 66 kA at 220/415 V AC 50/60 Hz · 66 kA at 440 V AC 50/60 Hz · 66 kA at 500/525 V AC 50/60 Hz · 66 kA at 660/690 V AC 50/60 Hz |
|---|
| [Icw] rated short-time withstand current | 66 kA 0.5 s · 66 kA 1 s · 36 kA 3 s |
|---|
| [Icm] rated short-circuit making capacity | 145 kA 220/415 V AC at 50/60 Hz · 145 kA 440 V AC at 50/60 Hz · 145 kA 500/525 V AC at 50/60 Hz · 145 kA 660/690 V AC at 50/60 Hz |
|---|
| Sensor rating | 800 A · 1000 A · 1250 A · 1600 A |
|---|
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz |
|---|
| [Uimp] rated impulse withstand voltage | 12 kV |
|---|
| Power dissipation in W | 390 W |
|---|
| Maximum breaking time | 25 ms |
|---|
| Maximum closing response time | 70 ms |
|---|
| Mounting support | Rails · Base plate |
|---|
| Upside connection | Front · Rear |
|---|
| Downside connection | Front · Rear |
|---|
| Connection pitch | 115 mm |
|---|
| Mechanical durability | 25000 cycles with periodic preventive maintenance |
|---|
| Electrical durability | 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 · 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 · AC-23A: 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-3 · AC-23A: 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-3 · AC-3: 6000 cycles 440/690 V AC 50/60 Hz conforming to EN/IEC 60947-3 |
|---|
| Height | Drawout circuit breaker with chassis: 439 mm · Drawout circuit breaker without chassis: 300 mm |
|---|
| Width | Drawout circuit breaker with chassis: 556 mm · Drawout circuit breaker without chassis: 493 mm |
|---|
| Depth | Drawout circuit breaker with chassis: 403 mm · Drawout circuit breaker without chassis: 300 mm |
|---|
| Product weight | 120 kg |
|---|
| Standards | EN/IEC 60947-1 · EN/IEC 60947-2 · EN/IEC 60947-2 Annex H · IEC 61557-12 |
|---|
| Product certifications | CE · IECEE CB Scheme |
|---|
| IP degree of protection | IP30 conforming to EN 60529 |
|---|
| Pollution degree | 3 conforming to IEC 60947-1 |
|---|
| Ambient air temperature for operation | -25…70 °C |
|---|
| Ambient air temperature for storage | -40…85 °C |
|---|
| Operating altitude | 0...2000 m without derating · 2000...5000 m with derating |
|---|
| Warranty (in months) | 18 |
|---|