- Range
- ComPact
- Product name
- ComPact NSX
- Range of product
- ComPact NSX100...250
- Device short name
- NSX100F
- Product or component type
- Circuit breaker
- Device application
- Distribution
- Number of poles
- 3P
- Protected poles description
- 3t
- [In] rated current
- 100 A at 40 °C
- [Ue] rated operational voltage
- 690 V AC 50/60 Hz
- Network type
- AC
- Network frequency
- 50/60 Hz
- Suitability for isolation
- Yes conforming to EN/IEC 60947-2
- Utilisation category
- Category A
- [Icu] rated ultimate short-circuit breaking capacity
- 10 kA at 600 V AC 50/60 Hz conforming to UL 508 · 25 kA at 480 V AC 50/60 Hz conforming to UL 508 · 85 kA at 240 V AC 50/60 Hz conforming to UL 508 · 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 · 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 · 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 · 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 · 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 · 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
- Performance level
- F 36 kA 415 V AC
- Trip unit name
- MicroLogic 2.2
- Trip unit technology
- Electronic
- Trip unit protection functions
- LSoI
- Control type
- Toggle
- Mechanical durability
- 50000 cycles
- Electrical durability
- 10000 cycles at 690 V In · 20000 cycles at 690 V In/2 · 30000 cycles at 440 V In · 50000 cycles at 440 V In/2
- Protection type
- L : for overload protection (long time) · So : for short time short-circuit protection with fixed delay · I : for instantaneous short-circuit protection
- Long-time pick-up adjustment type Ir (thermal protection)
- Adjustable 9 settings
- [Ir] long-time protection pick-up adjustment range
- 40...100 A
- Long-time protection delay adjustment type tr
- Fixed
- [tr] long-time protection delay adjustment range
- 11 s at 7.2 x Ir · 16 s at 6 x Ir · 400 s at 1.5 x Ir
- Thermal memory
- 20 minutes before and after tripping
- Short-time protection pick-up adjustment type Isd
- Adjustable 9 settings
- [Isd] Short-time protection pick-up adjustment range
- 1.5...10 x Ir
- Short-time protection delay adjustment type tsd
- Fixed
- Instantaneous protection pick-up adjustment type Ii
- Fixed
- [Ii] instantaneous protection pick-up adjustment range
- 1500 A
- Earth-leakage protection
- Without
- Zone selective interlocking ZSI
- Without
- Number of slots for electrical auxiliaries
- 5 slot(s)
- Local signalling
- Flashing LED (green) for ready to operate · LED 105 % Ir (red) for overload · LED 90 % Ir (orange) for overload