Schneider Electric MVS08H circuit breaker, rated 800 A. Circuit breaker, EasyPact MVS, 3 Poles, 800A, 65kA, EDO, ET5, drawout, electrical.
Circuit breaker, EasyPact MVS, 3 Poles, 800A, 65kA, EDO, ET5, drawout, electrical. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | EasyPact |
|---|
| Product name | MVS08H |
|---|
| Device short name | MVS08H |
|---|
| Product or component type | Circuit breaker |
|---|
| Device application | Distribution |
|---|
| Poles description | 3P |
|---|
| Protected poles description | 3P 3d |
|---|
| [In] rated current | 800 A at 40 °C |
|---|
| Network type | AC |
|---|
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Breaking capacity code | H |
|---|
| Suitability for isolation | Yes conforming to IEC 60947-2 |
|---|
| Utilisation category | Category B |
|---|
| Trip unit name | ET5S |
|---|
| Trip unit technology | Electronic |
|---|
| Trip unit rating | 800 A |
|---|
| Network frequency | 50/60 Hz |
|---|
| Control type | Electrically operated |
|---|
| Mounting mode | Drawout |
|---|
| Mounting support | Base plate · Rail |
|---|
| Connection position | Horizontal · Vertical |
|---|
| Location of connection | Rear |
|---|
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Uimp] rated impulse withstand voltage | 12 kV conforming to IEC 60947-2 |
|---|
| Circuit breaker CT rating | 800 A |
|---|
| Breaking capacity | 65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Ics] rated service breaking capacity | 65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Mechanical durability | 20000 cycles (with maintenance) conforming to IEC 60947-2 · 10000 cycles (without maintenance) conforming to IEC 60947-2 |
|---|
| Electrical durability | Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 · Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 |
|---|
| Connection pitch | 115 mm without spreader |
|---|
| Contact position indicator | Yes |
|---|
| [Icm] rated short-circuit making capacity | 143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Icw] rated short-time withstand current | 65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Trip unit protection functions | LSI |
|---|
| Protection type | Short time short-circuit protection · Instantaneous short-circuit protection · Overload protection (long time) |
|---|
| Fault indication | Short-circuit · Overload · Internal fault |
|---|
| Long time pick-up adjustment type Ir | Adjustable 9 settings |
|---|
| Long time pick-up adjustment range | 0.4...1 x In |
|---|
| Long time delay adjustment type | Adjustable 9 settings |
|---|
| [tr] long-time delay adjustment range | 0.5…24 s at 6 x Ir |
|---|
| Short-time pick-up adjustment type Isd | Adjustable 9 settings |
|---|
| [Isd] short-time pick-up adjustment range | 1.5...10 x Ir |
|---|
| Short-time delay adjustment type | Adjustable 5 settings |
|---|
| [tsd] short-time delay adjustment range | 100…400 ms |
|---|
| Instantaneous pick-up adjustment type Ii | Adjustable 9 settings |
|---|