Schneider Electric MasterPact MTZ2 circuit breaker, rated 1250 A. Circuit breaker frame, MasterPact MTZ2 12N1 fixed for MicroLogic X, 1250A, 42kA/415VAC (Icu), 3P.
Circuit breaker frame, MasterPact MTZ2 12N1 fixed for MicroLogic X, 1250A, 42kA/415VAC (Icu), 3P. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | MasterPacT |
|---|
| Product name | MasterPact MTZ2 |
|---|
| Device short name | MTZ2 12 N1 |
|---|
| Product or component type | Circuit breaker |
|---|
| Device application | Power distribution protection |
|---|
| Poles description | 3P |
|---|
| Control type | Without control unit |
|---|
| Product compatibility | control unit MicroLogic 2.0 X · control unit MicroLogic 5.0 X · control unit MicroLogic 6.0 X · control unit MicroLogic 7.0 X · control unit MicroLogic 2.0 Xi · control unit MicroLogic 5.0 Xi · control unit MicroLogic 6.0 Xi · control unit MicroLogic 7.0 Xi |
|---|
| [In] rated current | 1250 A at 40 °C |
|---|
| Breaking capacity code | N1 42 kA 415 V AC |
|---|
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
|---|
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
|---|
| Selectivity category | Category B |
|---|
| Mounting mode | Fixed |
|---|
| Breaking capacity | 42 kA at 220/415 V AC 50/60 Hz · 42 kA at 440 V AC 50/60 Hz · 42 kA at 500/525 V AC 50/60 Hz · 42 kA at 660/690 V AC 50/60 Hz |
|---|
| [Ics] rated service breaking capacity | 42 kA at 220/415 V AC 50/60 Hz · 42 kA at 440 V AC 50/60 Hz · 42 kA at 500/525 V AC 50/60 Hz · 42 kA at 660/690 V AC 50/60 Hz |
|---|
| [Icw] rated short-time withstand current | 42 kA 0.5 s · 42 kA 1 s · 22 kA 3 s |
|---|
| [Icm] rated short-circuit making capacity | 88 kA 220/415 V AC at 50/60 Hz · 88 kA 440 V AC at 50/60 Hz · 88 kA 500/525 V AC at 50/60 Hz · 88 kA 660/690 V AC at 50/60 Hz |
|---|
| Sensor rating | 630 A · 800 A · 1000 A · 1250 A |
|---|
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz |
|---|
| [Uimp] rated impulse withstand voltage | 12 kV |
|---|
| Power dissipation in W | 150 W |
|---|
| Maximum breaking time | 25 ms |
|---|
| Maximum closing response time | 70 ms |
|---|
| Mounting support | Rails · Base plate |
|---|
| Upside connection | Front · Rear |
|---|
| Downside connection | Front · Rear |
|---|
| Connection pitch | 115 mm |
|---|
| Mechanical durability | 25000 cycles with periodic preventive maintenance |
|---|
| Electrical durability | 10000 cycles 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 · 10000 cycles 690 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
|---|
| Height | 352 mm |
|---|
| Width | 422 mm |
|---|
| Depth | 300 mm |
|---|
| Product weight | 50 kg |
|---|
| Standards | EN/IEC 60947-1 · EN/IEC 60947-2 · EN/IEC 60947-2 Annex H · IEC 61557-12 |
|---|
| Product certifications | CE · IECEE CB Scheme |
|---|
| IP degree of protection | IP30 conforming to EN 60529 |
|---|
| Pollution degree | 3 conforming to IEC 60947-1 |
|---|
| Ambient air temperature for operation | -25…70 °C |
|---|
| Ambient air temperature for storage | -40…85 °C |
|---|
| Operating altitude | 0...2000 m without derating · 2000...5000 m with derating |
|---|
| Warranty (in months) | 18 |
|---|