Schneider Electric PowerLogic PM5000 power meter, rated 1 A. power meter PowerLogic PM5330, modbus, up to 31st Harmonic, 256KB 2DI/2DO 35 alarms.
power meter PowerLogic PM5330, modbus, up to 31st Harmonic, 256KB 2DI/2DO 35 alarms. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | PowerLogic |
|---|
| Product name | PowerLogic PM5000 |
|---|
| Product or component type | Power meter |
|---|
| Device short name | PM5330 |
|---|
| Power quality analysis | up to the 31st harmonic |
|---|
| Device application | Power monitoring · Multi-tariff |
|---|
| Type of measurement | Current · Voltage · Frequency · Power factor · Energy · Active and reactive power |
|---|
| [Us] rated supply voltage | 90...450 V AC 45...65 Hz · 100...300 V DC |
|---|
| Network frequency | 50 Hz · 60 Hz |
|---|
| [In] rated current | 1 A · 5 A |
|---|
| type of network | 3P + N · 3P · 1P + N |
|---|
| Maximum power consumption in VA | 11 VA at 415 V |
|---|
| Ride-through time | 80 ms 120 V AC typical · 100 ms 230 V AC typical · 100 ms 415 V AC typical · 50 ms 125 V DC typical |
|---|
| Display type | Monochrome graphic LCD |
|---|
| Display resolution | 128 x 128 pixels |
|---|
| Sampling rate | 64 samples/cycle |
|---|
| Measurement current | 5…8500 mA |
|---|
| Analogue input type | Voltage (impedance 5 MOhm) · Current (impedance <= 0.3 mOhm) |
|---|
| Measurement voltage | 35…760 V AC 45...65 Hz between phases · 20…400 V AC 45...65 Hz between phase and neutral |
|---|
| Frequency measurement range | 45…65 Hz |
|---|
| Number of inputs | 2 digital |
|---|
| Measurement accuracy | Active energy +/- 0.5 % · Reactive energy +/- 2 % · Active power +/- 0.5 % · Apparent power +/- 0.5 % · Frequency +/- 0.05 % · Power factor +/- 0.5 · Current +/- 0.5 % · Voltage +/- 0.5 % · Apparent energy +/- 0.5 % · Reactive power +/- 2 % |
|---|
| Accuracy class | Class 0.5S active energy conforming to IEC 62053-22 |
|---|
| Number of outputs | 2 relay · 2 digital |
|---|
| Information displayed | Tariff (4) |
|---|
| Communication port protocol | Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V · JBUS |
|---|
| Communication port support | RS485 |
|---|
| Data recording | Maintenance logs · Time stamping · Alarm logs · Data logs · Min/max of instantaneous values · Event logs |
|---|
| Memory capacity | 256 kB |
|---|
| Connections - terminals | Voltage circuit: screw terminal block4 · Control circuit: screw terminal block2 · Current transformer: screw terminal block6 · Input/output circuit: screw terminal block6 · Relay output: screw terminal block4 · Ethernet network: RJ45 connector |
|---|
| Mounting mode | Flush-mounted |
|---|
| Mounting support | Framework |
|---|
| Standards | UL 61010-1 · IEC 62053-22:2020 · IEC 61557-12:2015 · EN 50470-3 · IEC 60529 · IEC 62053-24 · EN 50470-1 · IEC 62053-23:2020 · IEC 62052-11:2020 · IEC 62052-31:2015 |
|---|
| Product certifications | CE conforming to IEC 61010-1 · CULus conforming to UL 61010-1 |
|---|
| Width | 96 mm |
|---|
| Depth | 72 mm |
|---|
| Height | 96 mm |
|---|
| Product weight | 430 g |
|---|
| Electromagnetic compatibility | Conducted and radiated emissions class B conforming to EN 55022 · Immunity to conducted disturbances - test level: 150 kHz...80 MHz level 4 conforming to IEC 61000-4-6 · Electrical fast transient/burst immunity test level 3 conforming to IEC 61000-4-4 · Radiated radio-frequency electromagnetic field immunity test level 4 conforming to IEC 61000-4-3 · Voltage dips and interruptions immunity test class B conforming to IEC 61000-4-11 · Limits for harmonic current emissions class A conforming to IEC 61000-3-2 · Electrostatic discharge level 4 conforming to IEC 61000-4-2 · Conducted RF disturbances level 3 conforming to IEC 61000-4-6 · Magnetic field at power frequency level 4 conforming to IEC 61000-4-8 · Immunity to conducted disturbances - test level: 150 kHz...80 MHz conforming to IEC 61000-4-6 · Electrical fast transient/burst immunity test conforming to IEC 61000-4-4 · Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 · Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 · Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3 · Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2 |
|---|
| IP degree of protection | IP54 display: conforming to IEC 60529 · IP30 rear: conforming to IEC 60529 |
|---|
| Relative humidity | 5…95 % at 50 °C non-condensing |
|---|
| Pollution degree | 2 |
|---|
| Ambient air temperature for operation | -25…70 °C meter |
|---|
| Ambient air temperature for storage | -40…85 °C |
|---|
| Operating altitude | 2000 m CAT III · 3000 m CAT II |
|---|