Schneider Electric Easy TeSys contactor, rated 40 A. Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3,<=440V,40A,110V AC coil,60Hz.
Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3,<=440V,40A,110V AC coil,60Hz. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | Easy TeSys |
|---|
| Range of product | Easy TeSys Control |
|---|
| Product or component type | Contactor |
|---|
| Device short name | LC1E |
|---|
| Contactor application | Motor control · Resistive load |
|---|
| Utilisation category | AC-3 · AC-3e · AC-1 |
|---|
| Poles description | 3P |
|---|
| [Ue] rated operational voltage | Power circuit: <= 690 V AC 50/60 Hz |
|---|
| [Ie] rated operational current | 40 A (at <55 °C) at <= 440 V AC AC-3 for power circuit · 40 A (at <55 °C) at <= 440 V AC AC-3e for power circuit · 60 A (at <55 °C) at <= 440 V AC AC-1 for power circuit |
|---|
| [Uc] control circuit voltage | 110 V AC 60 Hz |
|---|
| Motor power kW | 11 kW at 220/230 V AC · 18.5 kW at 380/400 V AC 50/60 Hz · 22 kW at 415/440 V AC · 22 kW at 500 V AC · 30 kW at 660/690 V AC · 30 kW at 660...690 V |
|---|
| Pole contact composition | 3 NO |
|---|
| [Ith] conventional free air thermal current | 60 A (at 55 °C) for power circuit |
|---|
| Irms rated making capacity | 520 A at 440 V AC for power circuit conforming to IEC 60947-4-1 |
|---|
| Rated breaking capacity | 340 A at 440 V for power circuit conforming to IEC 60947 |
|---|
| [Icw] rated short-time withstand current | 320 A 40 °C - 10 s for power circuit · 165 A 40 °C - 60 s for power circuit · 72 A 40 °C - 600 s for power circuit |
|---|
| Associated fuse rating | 80 A gG at <= 690 V coordination type 1 for power circuit · 10 A gG at <= 690 V for auxiliary contact circuit conforming to IEC 60947-5-1 |
|---|
| Average impedance | 1.5 mOhm - Ith 60 A 50 Hz for power circuit |
|---|
| Power dissipation per pole | 2.4 W AC-3 · 5.4 W AC-1 |
|---|
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-4-1 |
|---|
| Overvoltage category | III |
|---|
| Pollution degree | 3 |
|---|
| [Uimp] rated impulse withstand voltage | 6 kV coil not connected to the power circuit conforming to IEC 60947 |
|---|
| Mechanical durability | 5000000 cycles |
|---|
| Electrical durability | 350000 cycles AC-1 · 900000 cycles AC-3 |
|---|
| Control circuit type | AC at 60 Hz |
|---|
| Control circuit voltage limits | 0.85...1.1 Uc (-5…55 °C):operational 60 Hz · 0.3...0.6 Uc (-5…55 °C):drop-out 60 Hz |
|---|
| Inrush power in VA | 160 VA 50 Hz cos phi 0.75 (at 20 °C) · 140 VA 60 Hz cos phi 0.75 (at 20 °C) |
|---|
| Hold-in power consumption in VA | 15 VA 50 Hz cos phi 0.3 (at 20 °C) · 13 VA 60 Hz cos phi 0.3 (at 20 °C) |
|---|
| Heat dissipation | 6…10 W for control circuit |
|---|
| Operating time | 20...26 ms on closing · 8...12 ms on opening |
|---|
| Maximum operating rate | 1200 cyc/h 55 °C |
|---|
| Connections - terminals | Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible without cable end · Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable end · Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: flexible with cable end · Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: flexible with cable end · Power circuit: screw clamp terminals 1 2.5…25 mm² - cable stiffness: solid without cable end · Power circuit: screw clamp terminals 2 2.5…16 mm² - cable stiffness: solid without cable end · Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end · Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end · Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end · Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end · Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end · Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end |
|---|
| Tightening torque | Control circuit: 1.2 N.m · Power circuit: 5 N.m |
|---|
| Auxiliary contact composition | 1 NO + 1 NC |
|---|
| Minimum switching voltage | 17 V for auxiliary contact circuit |
|---|
| Minimum switching current | 5 mA for auxiliary contact circuit |
|---|
| Insulation resistance | > 10 MOhm for auxiliary contact circuit |
|---|
| Non-overlap time | 1.5 ms on energisation guaranteed between NC and NO contact · 1.5 ms on de-energisation guaranteed between NC and NO contact |
|---|
| Mounting support | DIN rail · Plate |
|---|
| Standards | EN/IEC 60947-1 · EN/IEC 60947-4-1 · EN/IEC 60947-5-1 · GB/T 14048.1 · GB/T 14048.4 · GB/T 14048.5 · EN/IEC 60335-1:Clause 30.2 · EN/IEC 60335-2-40:Annex JJ |
|---|
| Product certifications | CB Scheme · CCC · CE · EAC |
|---|
| IP degree of protection | IP2X conforming to IEC 60529 |
|---|
| Protective treatment | TH (pollution degree 3) conforming to IEC 60068-2-30 test Db |
|---|
| Permissible ambient air temperature around the device | -20…70 °C at Uc · -60…80 °C storage · -5…55 °C operation |
|---|