| Range | TeSys |
|---|
| Product or component type | Contactor |
|---|
| Device short name | LC1K |
|---|
| Device application | Control |
|---|
| Contactor application | Motor control |
|---|
| Utilisation category | AC-3 · AC-3e · AC-4 |
|---|
| Poles description | 3P |
|---|
| power pole contact composition | 3 NO |
|---|
| [Ue] rated operational voltage | Power circuit: <= 690 V AC <= 400 Hz · Signalling circuit: <= 690 V AC <= 400 Hz |
|---|
| [Ie] rated operational current | 6 A (at <60 °C) at <= 440 V AC AC-3 for power circuit · 6 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
|---|
| Control circuit type | AC at 50/60 Hz |
|---|
| [Uc] control circuit voltage | 380...400 V AC 50/60 Hz |
|---|
| Motor power kW | 1.5 kW at 220...230 V AC 50/60 Hz AC-3 · 2.2 kW at 380...415 V AC 50/60 Hz AC-3 · 3 kW at 440/690 V AC 50/60 Hz AC-3 · 1.5 kW at 220...230 V AC 50/60 Hz AC-3e · 2.2 kW at 380...415 V AC 50/60 Hz AC-3e · 3 kW at 440/690 V AC 50/60 Hz AC-3e · 1.5 kW at 220...230 V AC 50/60 Hz AC-4 · 2.2 kW at 380...415 V AC 50/60 Hz AC-4 · 3 kW at 440/690 V AC 50/60 Hz AC-4 |
|---|
| Auxiliary contact composition | 1 NC |
|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
|---|
| Overvoltage category | III |
|---|
| [Ith] conventional free air thermal current | 20 A (at 60 °C) for power circuit · 10 A (at 50 °C) for signalling circuit |
|---|
| Irms rated making capacity | 110 A AC for power circuit conforming to IEC 60947 · 110 A AC for signalling circuit conforming to IEC 60947 |
|---|
| Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947 · 110 A at 380...400 V conforming to IEC 60947 · 110 A at 415 V conforming to IEC 60947 · 110 A at 440 V conforming to IEC 60947 · 80 A at 500 V conforming to IEC 60947 · 70 A at 660...690 V conforming to IEC 60947 |
|---|
| [Icw] rated short-time withstand current | 90 A 50 °C - 1 s for power circuit · 85 A 50 °C - 5 s for power circuit · 80 A 50 °C - 10 s for power circuit · 60 A 50 °C - 30 s for power circuit · 45 A 50 °C - 1 min for power circuit · 40 A 50 °C - 3 min for power circuit · 20 A 50 °C - >= 15 min for power circuit · 80 A - 1 s for signalling circuit · 90 A - 500 ms for signalling circuit · 110 A - 100 ms for signalling circuit |
|---|
| Associated fuse rating | 25 A gG at <= 440 V for power circuit · 25 A aM for power circuit · 10 A gG for signalling circuit conforming to IEC 60947 · 10 A gG for signalling circuit conforming to VDE 0660 |
|---|
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
|---|
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to UL 508 · Power circuit: 690 V conforming to IEC 60947-4-1 · Signalling circuit: 690 V conforming to IEC 60947-4-1 · Signalling circuit: 690 V conforming to IEC 60947-5-1 · Signalling circuit: 600 V conforming to UL 508 · Power circuit: 600 V conforming to CSA C22.2 No 14 · Signalling circuit: 600 V conforming to CSA C22.2 No 14 |
|---|
| Insulation resistance | > 10 MOhm for signalling circuit |
|---|
| Inrush power in VA | 30 VA (at 20 °C) |
|---|
| Hold-in power consumption in VA | 4.5 VA (at 20 °C) |
|---|
| Heat dissipation | 1.3 W |
|---|
| Control circuit voltage limits | Operational: 0.8...1.15 Uc (at = 0.20 Uc (at <50 °C) |
|---|
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid · Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end · Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end · Screw clamp terminals 2 cable(s) 1.5…4 mm²solid · Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end · Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
|---|
| Maximum operating rate | 3600 cyc/h |
|---|
| Coil technology | Without built-in suppressor module |
|---|
| Auxiliary contacts type | type instantaneous 1 NC |
|---|
| Signalling circuit frequency | <= 400 Hz |
|---|
| Minimum switching current | 5 mA for signalling circuit |
|---|
| Minimum switching voltage | 17 V for signalling circuit |
|---|
| Mounting support | Rail · Plate |
|---|
| Tightening torque | 0.8…1.3 N.m - on screw clamp terminals Philips No 2 · 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm |
|---|
| Operating time | 10...20 ms coil de-energisation and NO opening · 10...20 ms coil energisation and NO closing |
|---|
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 · B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|---|
| Non overlap distance | 0.5 mm |
|---|
| Mechanical durability | 10 Mcycles |
|---|
| Electrical durability | 1.3 Mcycles 6 A AC-3 at Ue <= 440 V · 1.3 Mcycles 6 A AC-3e at Ue <= 440 V · 0.05 Mcycles 36 A AC-4 at Ue <= 440 V |
|---|
| Mechanical robustness | Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 · Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 · Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 · Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 · Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 · Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 · Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 · Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
|---|
| Height | 58 mm |
|---|
| Width | 45 mm |
|---|