Schneider Electric EasyPact CVS circuit breaker, rated 600 A. circuit breaker, EasyPact CVS, CVS630N , 50kA 380/415V, TMD, 4p/4d.
circuit breaker, EasyPact CVS, CVS630N , 50kA 380/415V, TMD, 4p/4d. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | EasyPact |
|---|
| Range of product | EasyPact CVS400...630 |
|---|
| Product name | EasyPact CVS |
|---|
| Device short name | CVS630N |
|---|
| Product or component type | Circuit breaker |
|---|
| Device application | Distribution |
|---|
| Poles description | 4P |
|---|
| Protected poles description | 4D |
|---|
| Earth leakage protection (Vigi add on) | Without |
|---|
| [In] rated current | 600 A at 50 °C |
|---|
| Network type | AC |
|---|
| Utilisation category | Category A |
|---|
| [Icu] Breaking capacity | 70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 · 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Trip unit name | TM-D |
|---|
| Trip unit technology | Thermal-magnetic |
|---|
| Trip unit rating | 600 A at 50 °C |
|---|
| Protection type | Overload protection (thermal) · Short-circuit protection (magnetic) |
|---|
| [Uimp] rated impulse withstand voltage | 8 kV conforming to EN/IEC 60947-2 |
|---|
| Network frequency | 50/60 Hz |
|---|
| Breaking capacity code | N |
|---|
| [Ics] rated service breaking capacity | 70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 · 32 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Neutral position | Left |
|---|
| Mechanical durability | 15000 cycles |
|---|
| Electrical durability | 4000 cycles 415 V In conforming to IEC 60947-2 |
|---|
| Control type | Toggle |
|---|
| Neutral protection setting | 1 x Ir (4D) |
|---|
| Long time pick-up adjustment type Ir | Adjustable |
|---|
| Long time pick-up adjustment range | 0.7...1 x In |
|---|
| Long time delay adjustment type | Fixed |
|---|
| Short-time delay adjustment type | Fixed |
|---|
| Instantaneous pick-up adjustment type Ii | Adjustable |
|---|
| Instantaneous pick-up adjustment range | 4...8 x In |
|---|
| Contact position indicator | Yes |
|---|
| Mounting support | Backplate |
|---|
| Mounting mode | Fixed |
|---|
| Upside connection | Front |
|---|
| Downside connection | Front |
|---|
| Connection pitch | 45 mm |
|---|
| Compatibility code | CVS630 |
|---|
| Width | 185 mm |
|---|
| Depth | 110 mm |
|---|
| Height | 255 mm |
|---|
| Standards | IEC 60947-2 · EN 60947-2 |
|---|
| Product certifications | IEC · GOST |
|---|
| Electrical shock protection class | Class II |
|---|