Schneider Electric TeSys CAD control relay, rated 10 A. Control relay, TeSys Deca, 5NO, 0 to 690V, 220VDC standard coil, screw clamp.
Control relay, TeSys Deca, 5NO, 0 to 690V, 220VDC standard coil, screw clamp. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | TeSys · TeSys Deca |
|---|
| Product name | TeSys CAD |
|---|
| Product or component type | Control relay |
|---|
| Device short name | CAD |
|---|
| Contactor application | Control circuit |
|---|
| Utilisation category | DC-13 · AC-15 · AC-14 |
|---|
| Pole contact composition | 5 NO |
|---|
| [Ue] rated operational voltage | <= 690 V AC 25...400 Hz |
|---|
| Control circuit type | DC standard |
|---|
| [Uc] control circuit voltage | 220 V DC |
|---|
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
|---|
| [Ith] conventional free air thermal current | 10 A (at 60 °C) |
|---|
| Irms rated making capacity | 140 A AC conforming to IEC 60947-5-1 · 250 A DC conforming to IEC 60947-5-1 |
|---|
| [Icw] rated short-time withstand current | 100 A - 1 s · 120 A - 500 ms · 140 A - 100 ms |
|---|
| Associated fuse rating | 10 A gG conforming to IEC 60947-5-1 |
|---|
| [Ui] rated insulation voltage | 600 V UL certified · 600 V CSA certified · 690 V conforming to IEC 60947-5-1 |
|---|
| Mounting support | Rail · Plate |
|---|
| Connections - terminals | Screw clamp terminals 1 cable(s) 1…4 mm²flexible without cable end · Screw clamp terminals 2 cable(s) 1…4 mm²flexible without cable end · Screw clamp terminals 1 cable(s) 1…4 mm²flexible with cable end · Screw clamp terminals 2 cable(s) 1…2.5 mm²flexible with cable end · Screw clamp terminals 1 cable(s) 1…4 mm²solid without cable end · Screw clamp terminals 2 cable(s) 1…4 mm²solid without cable end |
|---|
| Tightening torque | 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2 · 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm · 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
|---|
| Control circuit voltage limits | 0.1...0.25 Uc (-40…70 °C):drop-out DC · 0.7...1.25 Uc (-40…60 °C):operational DC · 1...1.25 Uc (60…70 °C):operational DC |
|---|
| Operating time | 53...72 ms coil energisation and NO closing · 16...24 ms coil de-energisation and NO opening |
|---|
| Mechanical durability | 30 Mcycles |
|---|
| Maximum operating rate | 180 cyc/mn |
|---|
| Time constant | 28 ms |
|---|
| Inrush power in W | 5.4 W (at 20 °C) |
|---|
| Hold-in power consumption in W | 5.4 W at 20 °C |
|---|
| Minimum switching voltage | 17 V |
|---|
| Minimum switching current | 5 mA |
|---|
| Non-overlap time | 1.5 ms on energisation between NC and NO contact · 1.5 ms on de-energisation between NC and NO contact |
|---|
| Insulation resistance | > 10 MOhm |
|---|
| Mechanical robustness | Shocks control relay open: 10 Gn for 11 ms conforming to IEC 60068-2-27 · Shocks control relay closed: 15 Gn for 11 ms conforming to IEC 60068-2-27 · Vibrations control relay open: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 · Vibrations control relay closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
|---|
| Height | 77 mm |
|---|
| Width | 45 mm |
|---|
| Depth | 93 mm |
|---|
| Product weight | 0.58 kg |
|---|
| Standards | EN/IEC 60947-5-1 · GB/T 14048.5 · UL 60947-5-1 · CSA C22.2 No 60947-5-1 · JIS C8201-5-1 |
|---|
| Product certifications | CB · CCC · UL · CSA · EAC · CE · UKCA |
|---|
| IP degree of protection | IP2X front face conforming to VDE 0106 |
|---|
| Protective treatment | TH conforming to IEC 60068 |
|---|
| Ambient air temperature for operation | -40…60 °C · 60…70 °C with derating |
|---|
| Ambient air temperature for storage | -60…80 °C |
|---|
| Operating altitude | 0...3000 m |
|---|
| Unit Type of Package 2 | S02 |
|---|
| Number of Units in Package 2 | 15 |
|---|
| Package 2 Height | 15 cm |
|---|