Schneider Electric discrete input module. discrete input module, Modicon X80, 16 isolated inputs, 200 to 240V AC.
discrete input module, Modicon X80, 16 isolated inputs, 200 to 240V AC. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range of product | Modicon X80 |
|---|
| Product or component type | Discrete input module |
|---|
| Device application | Industrial application |
|---|
| Discrete input number | 16 |
|---|
| Discrete input voltage | 200...240 V AC for isolated |
|---|
| Discrete input logic | Positive logic (sink) |
|---|
| Input wiring mode | 2 or 3 wires |
|---|
| Discrete input current | 3 mA at 200...240 V AC |
|---|
| Voltage state 1 guaranteed | >= 164 V |
|---|
| Voltage state 0 guaranteed | <= 40 V |
|---|
| Current state 1 guaranteed | >= 3 mA |
|---|
| Current state 0 guaranteed | <= 2 mA |
|---|
| Discrete input frequency | 50 Hz (47…63 Hz) · 60 Hz (47…63 Hz) |
|---|
| Input impedance | 28000 Ohm |
|---|
| Insulation resistance | > 10 MOhm 500 V DC |
|---|
| AC activation response time | 10 ms |
|---|
| AC deactivation response time | 20 ms |
|---|
| Sensor power supply | : 170…264 V |
|---|
| Typical current consumption | 76 mA DC |
|---|
| Current consumption | <= 126 mA at 3.3 V DC |
|---|
| Power dissipation in W | 5 W |
|---|
| Isolation between channels | 1780 Vrms for 1 minute |
|---|
| Isolation between channels and bus | 1780 Vrms for 1 minute |
|---|
| MTBF reliability | 3700000 H |
|---|
| Voltage detection threshold | 170 V AC sensor OK |
|---|
| Local signalling | 1 LED (green) for module operating (RUN) · 1 LED per channel (green) for channel diagnostic · 1 LED (red) for module error (ERR) · 1 LED (red) for module I/O |
|---|
| Height | 134.6 mm |
|---|
| Width | 32 mm |
|---|
| Depth | 86 mm |
|---|
| Product weight | 0.157 kg |
|---|
| IP degree of protection | IP20 |
|---|
| Protective treatment | Standard version |
|---|
| Marking | CE · UKCA · CULus · EAC · RCM |
|---|
| Standards | IEC 61131-2 |
|---|
| Dielectric strength | 1780 V AC at 50/60 Hz 1 min |
|---|
| Ambient air temperature for operation | 0…60 °C |
|---|
| Ambient air temperature for storage | -40…85 °C |
|---|
| Relative humidity | 5…95 % at 0…60 °C without condensation |
|---|
| Operating altitude | 0...2000 m · 2000...5000 m with derating |
|---|
| Pollution degree | 2 |
|---|
| Vibration resistance | 3 gn |
|---|
| Shock resistance | 30 gn |
|---|
| Unit Type of Package 2 | S03 |
|---|
| Number of Units in Package 2 | 8 |
|---|
| Package 2 Height | 30.000 cm |
|---|