Schneider Electric PowerLogic PM3000 power meter, rated 5 A. PM3255 power meter - 2 digital I - 2 digital O - RS485.
PM3255 power meter - 2 digital I - 2 digital O - RS485. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | PowerLogic |
|---|
| Product name | PowerLogic PM3000 |
|---|
| Product or component type | Power meter |
|---|
| Device short name | PM3255 |
|---|
| Market segment | Buildings small building cost management: billing: sub feeder · Buildings medium building cost management: billing: sub feeder · Buildings large building cost management: billing: sub feeder · Buildings multi-site cost management: billing: sub feeder · Data center cost management: billing: sub feeder · Healthcare cost management: billing: sub feeder · Industry cost management: billing: sub feeder · Buildings small building cost management: cost allocation: sub feeder · Buildings medium building cost management: cost allocation: sub feeder · Buildings large building cost management: cost allocation: sub feeder · Buildings multi-site cost management: cost allocation: sub feeder · Data center cost management: cost allocation: sub feeder · Healthcare cost management: cost allocation: sub feeder · Industry cost management: cost allocation: sub feeder |
|---|
| Power quality analysis | up to the 15th harmonic |
|---|
| Device application | Multi-tariff · Power monitoring · Sub billing |
|---|
| Type of measurement | Active and reactive power · Apparent power · Current · Voltage · Energy · Power factor · Frequency · Total current harmonic distortion THD (I) · Total voltage harmonic distortion THD (U) |
|---|
| supply voltage | 100...277 V AC 45...65 Hz · 173...480 V AC 45...65 Hz · 100...300 V DC |
|---|
| Network frequency | 60 Hz · 50 Hz |
|---|
| [In] rated current | 5 A · 1 A |
|---|
| type of network | 3P · 3P + N · 1P + N |
|---|
| Power consumption in VA | 5 VA |
|---|
| Display type | Backlit LCD |
|---|
| Display resolution | 128 x 96 pixels |
|---|
| Sampling rate | 32 samples/cycle |
|---|
| Measurement current | 0.02…1.2 A · 0.05…6 A |
|---|
| Analogue input type | Current 0...5 A · Current 0...1 A |
|---|
| Measurement voltage | 50…330 V AC 45...65 Hz direct · 50…330 V AC 45...65 Hz phase to neutral · 80…570 V AC 45...65 Hz direct · 80…570 V AC 45...65 Hz phase to phase · 570…999000 V AC 45...65 Hz with external VT |
|---|
| Frequency measurement range | 45…65 Hz |
|---|
| Number of inputs | 2 digital 0...4 mA 11...40 V DC |
|---|
| Measurement accuracy | Current 0.3 % 0.5...6 A · Current 0.5 % 0.1...1.2 A · Voltage 0.3 % 50...330 V · Voltage 0.3 % 80...570 V |
|---|
| Accuracy class | Class 0.5S active energy conforming to IEC 62053-22 · Class 1 active energy conforming to IEC 62053-21 · Class 2 reactive energy conforming to IEC 62053-23 · Class C active energy conforming to EN 50470-3 |
|---|
| Number of outputs | 2 digital (static) |
|---|
| Information displayed | Tariff (4) |
|---|
| Communication port protocol | Modbus at 9.6...38.4 kbauds |
|---|
| Communication port support | RS485 |
|---|
| Data recording | Energy consumption logs · 15 alarms · Power logs · Time stamping · Min/max of instantaneous values |
|---|
| Memory capacity | 512 KB |
|---|
| Mounting mode | Clip-on |
|---|
| Mounting support | DIN rail |
|---|
| Standards | BS EN 61557-12 · IEC 61557-12 · EN 61557-12 · BS EN 61326-1 · IEC 61326-1 · EN 61326-1 · BS EN 62052-11 · IEC 62052-11 · EN 62052-11 · BS EN 62053-21 · IEC 62053-21 · EN 62053-21 · BS EN 62053-22 · IEC 62053-22 · EN 62052-22 · BS EN 62053-23 · IEC 62053-23 · EN 62052-23 · BS EN 61010-1 · EN 61010-1 · IEC 61010-1 · UL 61010-1 · BS EN 61010-2-30 · IEC 61010-2-30 · EN 61010-2-30 · UL 61010-2-30 · ANSI C12.20 |
|---|
| Product certifications | CE conforming to IEC 61010-1 (safety) · CE conforming to EN 61557-12 (power monitor) · CE conforming to EN/IEC 61326-1 (EMC) · UKCA conforming to BS EN 61010-1 (safety) · UKCA conforming to BS EN 61557-12 (power monitor) · UKCA conforming to BS EN 61326-1 (EMC) · CULus conforming to EN 61010-1 (safety) · CULus conforming to UL 61010-1 (safety) · EAC (sub-meter) · RCM |
|---|
| Width | 90 mm |
|---|
| Depth | 70 mm |
|---|
| Height | 95 mm |
|---|
| Product weight | 0.26 kg |
|---|
| Electromagnetic compatibility | Electrostatic discharge level 4 conforming to IEC 61000-4-2 · Susceptibility to electromagnetic fields level 3 conforming to IEC 61000-4-3 · Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 · Surge immunity test level 4 conforming to IEC 61000-4-5 · Conducted RF disturbances level 3 conforming to IEC 61000-4-6 · Magnetic field at power frequency - test level: 0.5 mT conforming to IEC 61000-4-8 · Conducted and radiated emissions class B conforming to EN 55022 |
|---|
| Overvoltage category | III |
|---|
| IP degree of protection | IP40 front panel: conforming to IEC 60529 · IP20 body: conforming to IEC 60529 |
|---|
| Relative humidity | 5…95 % at 50 °C |
|---|
| Pollution degree | 2 |
|---|
| Ambient air temperature for operation | -25…70 °C |
|---|
| Ambient air temperature for storage | -40…85 °C |
|---|
| Operating altitude | < 3000 m |
|---|