Schneider Electric MVS20H circuit breaker, rated 2000 A. circuit breaker, EasyPacT MVS, 2000A, 65KA, 4Poles, MF, ET6.
circuit breaker, EasyPacT MVS, 2000A, 65KA, 4Poles, MF, ET6. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | EasyPact |
|---|
| Product name | MVS20H |
|---|
| Device short name | MVS20H |
|---|
| Product or component type | Circuit breaker |
|---|
| Device application | Distribution |
|---|
| Poles description | 4P |
|---|
| Protected poles description | 4P 4d |
|---|
| [In] rated current | 2000 A at 40 °C |
|---|
| Network type | AC |
|---|
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Breaking capacity code | H |
|---|
| Suitability for isolation | Yes conforming to IEC 60947-2 |
|---|
| Utilisation category | Category B |
|---|
| Trip unit name | ET6G |
|---|
| Trip unit technology | Electronic |
|---|
| Trip unit rating | 2000 A |
|---|
| Network frequency | 50/60 Hz |
|---|
| Control type | Manually operated |
|---|
| Mounting mode | Fixed |
|---|
| Mounting support | Base plate · Rail |
|---|
| Connection position | Vertical · Horizontal |
|---|
| Location of connection | Rear |
|---|
| [Ui] rated insulation voltage | 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Uimp] rated impulse withstand voltage | 12 kV conforming to IEC 60947-2 |
|---|
| Circuit breaker CT rating | 2000 A |
|---|
| Breaking capacity | 65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Ics] rated service breaking capacity | 65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Mechanical durability | 20000 cycles (with maintenance) conforming to IEC 60947-2 · 10000 cycles (without maintenance) conforming to IEC 60947-2 |
|---|
| Electrical durability | Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 · Category B: 5000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 |
|---|
| Connection pitch | 115 mm without spreader |
|---|
| Contact position indicator | Yes |
|---|
| [Icm] rated short-circuit making capacity | 143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 · 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Icw] rated short-time withstand current | 65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Trip unit protection functions | LSIG |
|---|
| Protection type | Overload protection (long time) · Short time short-circuit protection · Instantaneous short-circuit protection · Earth fault |
|---|
| Fault indication | Overload · Short-circuit · Earth fault · Internal fault |
|---|
| Long time pick-up adjustment type Ir | Adjustable 9 settings |
|---|
| Long time pick-up adjustment range | 0.4...1 x In |
|---|
| Long time delay adjustment type | Adjustable 9 settings |
|---|
| [tr] long-time delay adjustment range | 0.5…24 s at 6 x Ir |
|---|
| Short-time pick-up adjustment type Isd | Adjustable 9 settings |
|---|
| [Isd] short-time pick-up adjustment range | 1.5...10 x Ir |
|---|
| Short-time delay adjustment type | Adjustable 5 settings |
|---|
| [tsd] short-time delay adjustment range | 100…400 ms |
|---|
| Instantaneous pick-up adjustment type Ii | Adjustable 9 settings |
|---|