Schneider Electric Easy TeSys circuit breaker. Motor circuit breaker,Easy TeSys Power,GZ1E,AC-3,3P,4.6.3A,thermal magnetic trip.
Motor circuit breaker,Easy TeSys Power,GZ1E,AC-3,3P,4..6.3A,thermal magnetic trip. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | Easy TeSys |
|---|
| Range of product | Easy TeSys Power |
|---|
| Product or component type | Circuit breaker |
|---|
| Device short name | GZ1E |
|---|
| Device application | Motor |
|---|
| Trip unit technology | Thermal-magnetic |
|---|
| Suitability for isolation | Yes conforming to IEC 60947-1 appendix 7.1.6 |
|---|
| Colour | Grey (RAL 7011) |
|---|
| Poles description | 3P |
|---|
| Network type | AC |
|---|
| Utilisation category | AC-3 |
|---|
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
|---|
| Mounting mode | By clips · By screws |
|---|
| Mounting support | Rail |
|---|
| Mounting position | Any position |
|---|
| Motor power kW | 1.1 kW at 230 V AC 50/60 Hz · 2.2 kW at 400 V AC 50/60 Hz · 3 kW at 440 V AC 50/60 Hz · 3.7 kW at 500 V AC 50/60 Hz · 4 kW at 690 V AC 50/60 Hz |
|---|
| Breaking capacity | Icu: >= 100 kA at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 · Icu: >= 100 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 · Icu: 2 kA at 690 V AC 50/60 Hz conforming to IEC 60947-2 · Icu: 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 · Icu: 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 · 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 · 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 · 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 · 75 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Control type | Push-button |
|---|
| Thermal protection adjustment range | 4…6.3 A |
|---|
| Magnetic tripping current | 78 A |
|---|
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
|---|
| Power dissipation | 2.5 W (per pole) |
|---|
| Mechanical durability | 100000 cycles |
|---|
| Electrical durability | 100000 cycles for AC-3 |
|---|
| maximum operating rate | 25 cyc/h |
|---|
| Connections - terminals | Screw clamp terminals 2 1…6 mm² - cable stiffness: solid · Screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible without cable end · Screw clamp terminals 2 1…4 mm² - cable stiffness: flexible with cable end |
|---|
| Height | 89 mm |
|---|
| Width | 44.5 mm |
|---|
| Depth | 78 mm |
|---|
| Product weight | 0.26 kg |
|---|
| Standards | EN/IEC 60947-1 · EN/IEC 60947-2 · EN/IEC 60947-4-1 · GB/T 14048.1 · GB/T 14048.2 · GB/T 14048.4 · EN/IEC 60335-1:Clause 30.2 · EN/IEC 60335-2-40:Annex JJ |
|---|
| Product certifications | CB Scheme · CCC · CE · EAC |
|---|
| Protective treatment | TH |
|---|
| IP degree of protection | IP20 conforming to IEC 60529 |
|---|
| Ambient air temperature for operation | -20…60 °C |
|---|
| Ambient air temperature for storage | -40…80 °C |
|---|
| Fire resistance | 960 °C conforming to IEC 60695-2-1 |
|---|
| Operating altitude | 2000 m |
|---|
| Unit Type of Package 2 | S02 |
|---|
| Number of Units in Package 2 | 24 |
|---|
| Package 2 Height | 15.000 cm |
|---|
| Package 2 Width | 30.000 cm |
|---|