Schneider Electric external power supply module. External power supply module, input voltage 110VAC to 130VAC 50/60Hz, output voltage 24VDC, output current 1A.
External power supply module, input voltage 110VAC to 130VAC 50/60Hz, output voltage 24VDC, output current 1A. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Product or component type | External power supply module |
|---|
| Device application | Power supply |
|---|
| Range compatibility | Masterpact MasterPact MTZ · Masterpact MasterPact NT · Masterpact MasterPact NW · ComPact ComPact NSX · ComPact ComPact NSX DC · ComPact ComPact NS630b...1600 · ComPact ComPact NS1600b...3200 · PowerPact PowerPact H · PowerPact PowerPact J · PowerPact PowerPact L · PowerPact PowerPact P · PowerPact PowerPact R |
|---|
| Accessory / separate part type | Trip unit accessories · Control units accessories |
|---|
| Trip unit name | MicroLogic |
|---|
| Power supply type | Regulated switch mode |
|---|
| [Us] rated supply voltage | 110...130 V AC 50/60 Hz tolerance: +10 % -15 % |
|---|
| Input voltage limits | 93.5...143 V AC at 47.5…63 Hz |
|---|
| Output voltage | 24 V DC +/-5 % |
|---|
| Overvoltage category | IV conforming to IEC 62477-1 · IV conforming to UL 61010-1 |
|---|
| Power supply output current | 1 A |
|---|
| Rated power in W | 24 W |
|---|
| Output protection type | Against overload, protection technology: manual reset · Against overvoltage, protection technology: 30...32 V, manual reset · Against short-circuits, protection technology: manual reset · Thermal, protection technology: automatic reset |
|---|
| Inrush current | 20 A 2 ms |
|---|
| Efficiency | 85 % |
|---|
| Power dissipation in W | 4.2 W |
|---|
| Holding time | >= 20 ms 110...130 V AC |
|---|
| Permissible temporary current boost | 1.5 A (200 ms) |
|---|
| Connections - terminals | Screw type terminals, connection capacity: 2 x 0.2...2 x 1.5 mm² 24 AWG...16 AWG · Screw type terminals, connection capacity: 1 x 0.2...1 x 4 mm² 24 AWG...12 AWG |
|---|
| Mounting support | 35 x 7.5 mm symmetrical DIN rail |
|---|
| Operating position | Horizontal |
|---|
| Operating altitude | 0...2000 m |
|---|
| Name of test | Electrostatic discharges conforming to EN/IEC 61000-4-2 · Induced electromagnetic field conforming to EN/IEC 61000-4-6 · Magnetic field conforming to EN 61000-4-8 · Primary outage conforming to IEC 61000-4-29 · Radiated electromagnetic field conforming to EN/IEC 61000-4-3 · Rapid transient conforming to IEC 61000-4-4 · Surge conforming to EN/IEC 61000-4-5 · Radiated emissions conforming to EN 61000-6-3 · Conducted emissions on the power line conforming to EN 61000-6-3 |
|---|
| Status LED | 1 LED (green) output voltage |
|---|
| Height | 90 mm |
|---|
| Width | 108 mm |
|---|
| Depth | 67.5 mm |
|---|
| Standards | UL 61010-1 · IEC 62477-1 |
|---|
| Marking | EAC · CE · UL |
|---|
| Environmental characteristic | EMC conforming to EN/IEC 61000-6-2 · EMC conforming to EN/IEC 61000-6-3 · Safety conforming to IEC 62477-1 · Safety conforming to SELV |
|---|
| IP degree of protection | IP4X (front face) conforming to EN/IEC 60529 · IP2X (connection terminals) conforming to EN/IEC 60529 · IP3x (housing) conforming to EN/IEC 60529 |
|---|
| Ambient air temperature for operation | -25…70 °C |
|---|
| Ambient air temperature for storage | -50…85 °C |
|---|
| Relative humidity | 0…95 % during operation · 0…95 % in storage |
|---|
| Dielectric strength | 3000 V between input and ground · 3000 V between input and output · 1500 V between output and ground |
|---|
| Compatibility code | CB_EXTERNAL_POWERSUPPLY |
|---|
| Unit Type of Package 2 | S03 |
|---|
| Number of Units in Package 2 | 23 |
|---|
| Package 2 Height | 30.0 cm |
|---|
| Package 2 Width | 30.0 cm |
|---|
| Package 2 Length | 40.0 cm |
|---|
| Package 2 Weight | 9.062 kg |
|---|
| Warranty (in months) | 18 |
|---|