Schneider Electric discrete input module. Discrete input module, Modicon X80, 32 inputs, 12/24V DC positive or negative, for severe environments.
Discrete input module, Modicon X80, 32 inputs, 12/24V DC positive or negative, for severe environments. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range of product | Modicon X80 |
|---|
| Product or component type | Discrete input module |
|---|
| Device application | Industrial application in severe environment |
|---|
| Discrete input number | 32 |
|---|
| Discrete input voltage | 12 V DC for isolated · 24 V DC for isolated |
|---|
| Discrete input logic | Positive or negative |
|---|
| Input wiring mode | 2 or 3 wires |
|---|
| Discrete input current | 3.3 mA at 12 V DC · 3.3 mA at 24 V DC |
|---|
| Voltage state 1 guaranteed | >= 10 V · <= -10 V |
|---|
| Voltage state 0 guaranteed | = -5 V |
|---|
| Current state 1 guaranteed | >= 2 mA |
|---|
| Current state 0 guaranteed | <= 1.5 mA |
|---|
| Input impedance | 7270 Ohm |
|---|
| Insulation resistance | > 10 MOhm 500 V DC |
|---|
| DC typical response time | 4 ms |
|---|
| DC maximum response time | 7 ms |
|---|
| Paralleling of outputs | Yes |
|---|
| Sensor power supply | : 19…30 V |
|---|
| Typical current consumption | 100 mA DC · 7.6 mA at 24 V DC |
|---|
| Current consumption | 130 mA at 3.3 V DC · at 24 V DC |
|---|
| Power dissipation in W | 4.7 W |
|---|
| Isolation between channels and bus | 1500 V for 1 minute |
|---|
| Hot swapping fallback | Yes |
|---|
| MTBF reliability | 2200000 H |
|---|
| Voltage detection threshold | 19 V DC sensor OK |
|---|
| Local signalling | 1 LED (green) for module operating (RUN) · 1 LED per channel (green) for channel diagnostic · 1 LED (red) for module error (ERR) · 1 LED (red) for module I/O |
|---|
| Height | 134.6 mm |
|---|
| Width | 32 mm |
|---|
| Depth | 86 mm |
|---|
| Product weight | 0.138 kg |
|---|
| IP degree of protection | IP20 |
|---|
| Protective treatment | Conformal coating |
|---|
| Marking | CE · UKCA · CULus · RCM · EAC |
|---|
| Product certifications | ATEX zone 2 · IECEx zone 2 · CCC Ex zone 2 (pending) · CULus HazLoc |
|---|
| Standards | IEC 61131-2 |
|---|
| Directives | 2014/35/EU - low voltage directive · 2014/30/EU - electromagnetic compatibility |
|---|
| Dielectric strength | 1500 V AC at 50/60 Hz 1 minute, primary/secondary · 1500 V AC at 50/60 Hz 1 minute, between group of channels |
|---|
| Ambient air temperature for operation | -25…70 °C |
|---|
| Ambient air temperature for storage | -40…85 °C |
|---|
| Relative humidity | 5…95 % at -25…70 °C without condensation |
|---|
| Operating altitude | 0...2000 m · 2000...5000 m with derating |
|---|
| Pollution degree | 2 |
|---|
| Environmental characteristic | Gas resistant class Gx · Gas resistant class 3C4 · Dust resistant class 3S4 · Sand resistant class 3S4 · Salt resistant level 2 · Mold growth resistant class 3B2 · Fungal spore resistant class 3B2 |
|---|
| Vibration resistance | 3 gn |
|---|
| Shock resistance | 30 gn |
|---|