Schneider Electric discrete output module kit. Discrete Output Module + Base, 2 Isolated Out, 24V DC, 2A, Source, Protected, 1/2/3 Wires, Hardened, Modicon Edge I/O NTS.
Discrete Output Module + Base, 2 Isolated Out, 24V DC, 2A, Source, Protected, 1/2/3 Wires, Hardened, Modicon Edge I/O NTS. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range of product | Modicon Edge I/O NTS |
|---|
| Product or component type | Discrete output module kit |
|---|
| Kit composition | NTSDDO0212H module · NTSXBA0100H base |
|---|
| Mandatory accessory | NTSXTB12_1_H terminal block |
|---|
| Product compatibility | NTSN..... |
|---|
| Range compatibility | Logic/motion controller - Modicon M262 · Modicon M580 · Third party |
|---|
| Device application | Industrial application in severe environment |
|---|
| Discrete output number | 2 |
|---|
| Group of output channels | 2 groups of 1 channels |
|---|
| Discrete output logic | Positive logic (source) |
|---|
| Discrete output voltage | 24 V DC |
|---|
| Operating mode | Synchronous/Isochronous |
|---|
| Output wiring mode | 1, 2 or 3 wires |
|---|
| Discrete output current | 2 A per channel · 4 A per module |
|---|
| Discrete output frequency | 1 kHz for resistive load · 0.5/LI² Hz for inductive load |
|---|
| Response time on output | 70 µs turn-on · 120 µs turn-off |
|---|
| Maximum leakage current | 0.0001 mA per channel |
|---|
| Maximum voltage drop | <0.25 V per channel (from external power supply) for DC · <0.35 V per channel (from internal power distribution module) for DC |
|---|
| Maximum tungsten load | <48 W |
|---|
| Paralleling of outputs | Yes for redundancy · Yes for double current · Yes for same group (maxium 2) |
|---|
| Output protection type | Transient voltage suppression per channel · Short circuit protection per channel · Overload/thermal protection per channel · Reverse polarity protection for internal supply per module |
|---|
| Output diagnostic | Power supply error per channel · External power supply error per channel · Short circuit error per channel |
|---|
| Power supply type | Bus power from power supply bus (24 Vdc) · Field power from power supply field (24 Vdc) · Optional field power from external power supply (24 Vdc) |
|---|
| Rated operational voltage limits | 20.4...28.8 V DC |
|---|
| Typical current consumption | 27.6 mA at 24 V DC on the Bus current · 0 mA at 24 V DC on the internal field current minimum · 4000 mA at 24 V DC on the internal field current maximum |
|---|
| Electrical connection | Screw/spring terminal block |
|---|
| Power dissipation in W | 1.22 W maximum at 24 V DC |
|---|
| Isolation between channels | 500 V AC |
|---|
| Isolation between channels and bus | 1500 V AC |
|---|
| Isolation between channels and ground | 1500 V AC |
|---|
| Hot swapping fallback | Yes |
|---|
| Local signalling | 1 LED (green) for module operating (RUN) · 1 LED per channel (green) for channel diagnostic · 1 LED (red) for module error (ERR) |
|---|
| Housing colour | Grey |
|---|
| Mounting support | Top hat type TH35-7.5 rail conforming to IEC 60715 · Top hat type TH35-15 rail conforming to IEC 60715 |
|---|
| Height | 100 mm |
|---|
| Width | 15 mm |
|---|
| Depth | 80 mm |
|---|
| Product weight | 0.073 kg |
|---|
| IP degree of protection | IP20 |
|---|
| Protective treatment | Conformal coating |
|---|
| Marking | CE · UKCA · CULus · RCM |
|---|
| Product certifications | CE · UKCA · CULus · RCM · Merchant Navy - EU RO MR (pending) · EAC (pending) · ATEX Zone 2 (pending) · IECEx zone 2 (pending) · CCC Ex zone 2 (pending) |
|---|
| Standards | EN/IEC 61131-2 · EN 61010-2-201 · UL 61010-2-201 · IACS E10 · EN/IEC 61000-6-5, interface type 1 and type 2 · EN/IEC 61850-3, location G · EN/IEC 60079-0 · EN 50155 · EN 50121-4 · EN 50121-5 |
|---|
| Directives | 2014/30/EU - electromagnetic compatibility · 2014/34/EU - ATEX directive · 2014/35/EU |
|---|
| Ambient air temperature for operation | -40…70 °C |
|---|