| Range of product | Modicon M580 |
|---|
| Product or component type | Communication module |
|---|
| Device application | OPC UA server & IT control network |
|---|
| Product compatibility | Modicon M580 standalone CPU (BMEP58…..) · Modicon M580 Redundant CPU (BMEH58…..) · Modicon M580 safety CPU (non interfering type 1) (BMEP582…..) · Modicon M580 safety Redundant CPU (non interfering type 1) (BMEH582…..) · Modicon X80 Rack with Ethernet backplane (BMEXBP…..) |
|---|
| Mounting location | Main rack |
|---|
| Backplane slot location | Ethernet + X-bus Slot |
|---|
| Slot occupied by module | 1 |
|---|
| Maximum number of modules per rack | 2 |
|---|
| Supply | Internal power supply via rack |
|---|
| Integrated connection type | 1 Ethernet, connector type: RJ45, transmission rate: 10/100/1000 Mbit/s, transmission mode: double shielded twisted pair |
|---|
| Exchange mode | Half duplex and full duplex |
|---|
| Transmission support medium | Ethernet backplane |
|---|
| OPC UA | OPC UA server · 10 clients connection max · 50000 monitored item max in standard sampling mode · 2000 monitored item max in fast sampling mode · 40 maximum subscriptions per session · 250 ms, minimum publishing interval in standard sampling mode · 20 ms, minimum sampling interval in fast sampling mode · 20 ms, minimum publishing interval in fast sampling mode · 125 ms, sampling interval in standard sampling mode · 100000, maximum number of nodes · Hot redundancy mode |
|---|
| Source timestamping | Only digital IOs or variables · 250 ms, minimum polling of buffer · 5000 ms, maximum polling of buffer |
|---|
| Network | IPV6 · IP forwarding (Front port and backplane) · Service forwarding · Network segmentation |
|---|
| Communication service | Modbus TCP server for module diagnostics · Network management SNMP agent V1 and V3 · Time synchronization NTP V4 - Client and Server |
|---|
| Cybersecurity | Secure communication (HTTPS) · Built-in firewall · Certificate based authentication · System hardening · Certificate management (self-signed and PKI) · Role-based access control · Syslog protocol support · IPSec (initiator and responder role) · Network physical isolation · Achilles level 2 tested |
|---|
| Function available | CCOTF (configuration change on the fly) · Hot swappable module · Advanced diagnostic information (DDT, web pages, OPC UA objects) · SCADA connection through Modbus TCP |
|---|
| Web server | For commissioning, operational and maintenance |
|---|
| Current consumption | 155 mA at 24 V DC |
|---|
| Local signalling | 1 LED (green) for processor running (RUN) · 1 LED (red) for processor or system fault (ERR) · 1 LED (green/red) for ETH MS (Ethernet port configuration status) · 1 LED (green/red) for Eth NS (Ethernet network status) · 1 LED (green/red) for status (STS) · 1 LED (yellow) for communication data bus |
|---|
| Width | 32 mm |
|---|
| Height | 131 mm |
|---|
| Length | 86.05 mm |
|---|
| Product weight | 0.4 kg |
|---|
| IP degree of protection | IP20 |
|---|
| Protective treatment | Conformal coating |
|---|
| Ambient air temperature for operation | -25…70 °C |
|---|
| Ambient air temperature for storage | -40…85 °C |
|---|
| Relative humidity | 5…95 % at 55 °C without condensation |
|---|
| Operating altitude | 0...2000 m · 2000 m...5000 m with derating factor |
|---|
| vibration resistance | 3 gn |
|---|
| Shock resistance | 30 gn |
|---|
| Marking | CE |
|---|
| Product certifications | CE · UL · CSA · RCM · EAC · Merchant Navy · ATEX · IECEx |
|---|
| Standards | IEC 61131-2 · IEC 61010-2-201 · UL 61010-2-201 · CSA C22.2 No 61010-2-201 · IACS E10 · IEC 61000-6-5, interface type 1 and type 2 · IEC 61850-3, location G |
|---|
| Directives | 2014/35/EU - low voltage directive · 2014/30/EU - electromagnetic compatibility |
|---|
| Environmental characteristic | Hazardous location class I division 2 |
|---|
| Unit Type of Package 2 | S02 |
|---|
| Number of Units in Package 2 | 4 |
|---|
| Package 2 Height | 15 cm |
|---|
| Package 2 Width | 30 cm |
|---|
| Package 2 Length | 40 cm |
|---|
| Package 2 Weight | 2.434 kg |
|---|
| Unit Type of Package 3 | P12 |
|---|