Schneider Electric shunt trip release. shunt trip release, Acti9, iMX, voltage release, 100..415 V AC.
shunt trip release, Acti9, iMX, voltage release, 100...415 V AC. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| range of product | Acti9 |
|---|
| Product or component type | Shunt trip release |
|---|
| Device short name | iMX |
|---|
| [Uc] control circuit voltage | 110...415 V AC 50/60 Hz · 110...130 V DC |
|---|
| 9 mm pitches | 2 |
|---|
| Range compatibility | Acti9 iC60H RCBO · Acti9 iC60H RCBO PoN · Acti9 iC60H2 RCBO · Acti9 iC60N RCBO · Acti9 iKQE RCBO · Acti9 iCVm40 · Acti9 iCVr40 · Acti9 iDDm40 |
|---|
| Local signalling | Action indicator |
|---|
| Mounting mode | Clip-on |
|---|
| Mounting support | DIN rail |
|---|
| Comb busbar and distribution block compatibility | Top and bottom: YES |
|---|
| Width | 18 mm |
|---|
| Colour | White |
|---|
| Connections - terminals | Clamp terminal - 2 cable(s) 2.5 mm² - flexible with cable end · Clamp terminal - 1 cable(s) 6 mm² - rigid · Clamp terminal - 2 cable(s) 2.5 mm² - rigid · Clamp terminal - 1 cable(s) 4 mm² - flexible |
|---|
| Tightening torque | 1 N.m |
|---|
| Standards | EN/IEC 60947-1 |
|---|
| Tropicalisation | 2 conforming to EN/IEC 60947-5-1 |
|---|
| Relative humidity | 95 % at 55 °C |
|---|
| Ambient air temperature for operation | -35…70 °C |
|---|
| Ambient air temperature for storage | -40…85 °C |
|---|
| Unit Type of Package 2 | BB1 |
|---|
| Number of Units in Package 2 | 8 |
|---|
| Package 2 Height | 8.5 cm |
|---|
| Package 2 Width | 10 cm |
|---|
| Package 2 Length | 27 cm |
|---|
| Package 2 Weight | 633 g |
|---|
| Unit Type of Package 3 | S03 |
|---|
| Number of Units in Package 3 | 72 |
|---|
| Package 3 Height | 30 cm |
|---|
| Package 3 Width | 30 cm |
|---|
| Package 3 Length | 40 cm |
|---|
| Package 3 Weight | 6.111 kg |
|---|
| Warranty (in months) | 18 |
|---|