Schneider Electric TeSys VARIO, rated 8.1 A. Switch disconnector,TeSys Control,for ON/emergency stop,12A(V02),4 screws fixing,for mounting at back of an enclosure.
Switch disconnector,TeSys Control,for ON/emergency stop,12A(V02),4 screws fixing,for mounting at back of an enclosure. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | TeSys |
|---|
| Product Name | TeSys VARIO |
|---|
| Device Short Name | VCCF |
|---|
| Product Type | Emergency stop switch disconnector |
|---|
| Device Composition | Shaft extension · Handle · Switch |
|---|
| Mounting Support | Handle: door · Switch: symmetrical rail · Switch: plate |
|---|
| Mounting Method | By 4 screws for handle · By clips for switch · By screws for switch |
|---|
| Performance Level | High performance |
|---|
| Number of Poles | 3P |
|---|
| Contact Type and Composition | 3 NO |
|---|
| [Ue] IEC Rated Operational Voltage | 690 V AC 50/60 Hz |
|---|
| IEC Rated Operational Power in W | 3 kW at 400...415 V (AC-3) · 4 kW at 500 V (AC-3) · 1.5 kW at 230...240 V (AC-3) · 5.5 kW at 500 V (AC-23A) · 5.5 kW at 690 V (AC-3) · 7.5 kW at 690 V (AC-23A) · 3 kW at 230...240 V (AC-23A) · 4 kW at 400...415 V (AC-23A) |
|---|
| [Ie] Rated Operational Current | 8.1 A AC-23 Ue: 400 V |
|---|
| [Ith] Conventional Free Air Thermal Current | 12 A |
|---|
| [Ithe] Conventional Enclosed Thermal Current | 10 A |
|---|
| Making Capacity ( I Rms) | 120 A at 400 V AC-21A · 120 A at 400 V AC-22A · 120 A at 400 V AC-23A |
|---|
| Breaking Capacity | 120 A at 400 V (AC-21A) · 120 A at 400 V (AC-22A) · 120 A at 400 V (AC-23A) |
|---|
| Rated Conditional Short Circuit Current | 10 kA at 400 V - associated fuse 12 A aM · 10 kA at 400 V - associated fuse 12 A gG |
|---|
| [Icm] Rated Short Circuit Making Capacity | 1 kA at 400 V at Ipeak |
|---|
| [Icw] Rated Short Time Withstand Current | 300 A at 400 V duration: 1 s |
|---|
| [Uimp] Rated Impulse Withstand Voltage | 8 kV |
|---|
| Suitability for Isolation | Yes |
|---|
| Network Type | AC · DC |
|---|
| Intermittent Duty Class | 30 |
|---|
| Control Type | Rotary handle |
|---|
| Rotary Handle Mounting Style | Extended |
|---|
| Handle Color | Red |
|---|
| Handle Front Plate Color | Yellow |
|---|
| Rotary Handle Padlocking | 1 to 3 padlocks 4…8 mm |
|---|
| Marking | 0 - 1 |
|---|
| Mechanical Durability | 100000 cycles |
|---|
| Electrical Durability | 100000 cycles AC-21 · 30000 cycles DC-1 · 30000 cycles DC-2 · 30000 cycles DC-3 · 30000 cycles DC-4 · 30000 cycles DC-5 |
|---|
| IEC Terminal Connection | Power circuit: screw clamp terminals10 mm² - solid · Power circuit: screw clamp terminals6 mm² - flexible - with cable end |
|---|
| Tightening Torque | Power circuit: 2.1 N.m - on screw clamp terminals |
|---|
| Base Dimension | 60 x 60 mm |
|---|
| Height | 74 mm |
|---|
| Width | 60 mm |
|---|
| Product Weight | 0.527 kg |
|---|
| Standards | IEC 60947-3 |
|---|
| Product Certifications | CCC · UL · CSA · GL · UKCA |
|---|
| Degree of Protection | IP20 conforming to IEC 60529 · IP65 |
|---|
| Protective Treatment | TC |
|---|
| Mechanical Robustness | Vibrations 10...150 Hz (1 gn) conforming to IEC 60068-2-6 · Shocks 11 ms (30 Gn) conforming to IEC 60068-2-27 |
|---|
| Ambient Air Temperature for Operation | -20…50 °C |
|---|
| Fire Resistance | 960 °C conforming to IEC 60695-2-1 |
|---|