Schneider Electric ComPacT control unit. Control unit MicroLogic 2.0E, ComPacT NS630b to NS1600 withdrawable and manually operated, basic protections.
Control unit MicroLogic 2.0E, ComPacT NS630b to NS1600 withdrawable and manually operated, basic protections. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | ComPacT |
|---|
| Range of product | ComPacT NS630b...1600 new generation |
|---|
| Product or component type | Control unit |
|---|
| Trip unit name | MicroLogic 2.0 E |
|---|
| Trip unit technology | Electronic |
|---|
| Range compatibility | ComPacT NS630b...1600 |
|---|
| Device application | Distribution |
|---|
| Number of poles | 4P · 3P |
|---|
| Protected poles description | 4t · 3t · 3t + N/2 |
|---|
| Trip unit protection functions | Basic protection |
|---|
| Protection type | L : for overload protection (long time) · I : for instantaneous short-circuit protection |
|---|
| Trip unit rating | 630 A at 50 °C · 800 A at 50 °C · 1000 A at 50 °C · 1250 A at 50 °C · 1600 A at 50 °C |
|---|
| Network type | AC |
|---|
| Network frequency | 50/60 Hz |
|---|
| Circuit breaker mounting mode | Withdrawable |
|---|
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
|---|
| [Ir] long-time protection pick-up adjustment range | 0.4...1 x In |
|---|
| Long-time protection delay adjustment type tr | Adjustable 9 settings |
|---|
| [tr] long-time protection delay adjustment range | 0.7…16.6 s at 7.2 x Ir · 0.7…24 s at 6 x Ir · 12.5…600 s at 1.5 x Ir |
|---|
| Thermal memory | 20 mn |
|---|
| Instantaneous protection pick-up adjustment type Ii | Adjustable 9 settings |
|---|
| [Ii] instantaneous protection pick-up adjustment range | 1.5...10 x Ir |
|---|
| Earth-leakage protection | Without |
|---|
| Zone selective interlocking ZSI | Without |
|---|
| Local signalling | 3 LEDs (red) for electrical fault · 1 LED (red) for internal error · 1 LED (yellow) for overload |
|---|
| Display type | Digital display |
|---|
| Type of measurement | Energy meter |
|---|
| Communication of data | Measurement readout · Protection and alarm settings |
|---|
| Standards | IEC 60947-4-2 |
|---|
| Ambient air temperature for operation | -25…70 °C |
|---|
| Ambient air temperature for storage | -25…85 °C |
|---|
| Warranty (in months) | 18 |
|---|