Schneider Electric TeSys GV2 motor circuit breaker, rated 1.6 A. Motor circuit breaker, TeSys Deca, 3P, 1 to 1.6A, thermal magnetic, screw clamp terminals, rotary handle.
Motor circuit breaker, TeSys Deca, 3P, 1 to 1.6A, thermal magnetic, screw clamp terminals, rotary handle. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | TeSys Deca |
|---|
| Product name | TeSys GV2 |
|---|
| Product or component type | Motor circuit breaker |
|---|
| Device short name | GV2P |
|---|
| Device application | Motor protection |
|---|
| Trip unit technology | Thermal-magnetic |
|---|
| Poles description | 3P |
|---|
| Network type | AC |
|---|
| Utilisation category | Category A conforming to IEC 60947-2 · AC-3 conforming to IEC 60947-4-1 · AC-3e conforming to IEC 60947-4-1 |
|---|
| Network frequency | 50/60 Hz conforming to IEC 60947-2 |
|---|
| Motor power kW | 0.37 kW at 400/415 V AC 50/60 Hz · 0.55 kW at 400/415 V AC 50/60 Hz · 0.37 kW at 500 V AC 50/60 Hz · 0.55 kW at 500 V AC 50/60 Hz · 0.75 kW at 690 V AC 50/60 Hz |
|---|
| Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 · 100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 · 100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 · 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 · 100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Ics] rated service short-circuit breaking capacity | 100 % at 230/240 V AC 50/60 Hz conforming to IEC 60947-2 · 100 % at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 · 100 % at 440 V AC 50/60 Hz conforming to IEC 60947-2 · 100 % at 500 V AC 50/60 Hz conforming to IEC 60947-2 · 100 % at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Control type | Rotary handle |
|---|
| [In] rated current | 1.6 A |
|---|
| Thermal protection adjustment range | 1…1.6 A conforming to IEC 60947-2 |
|---|
| Magnetic tripping current | 26.2 A |
|---|
| [Ith] conventional free air thermal current | 1.6 A conforming to IEC 60947-2 |
|---|
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-2 |
|---|
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
|---|
| Suitability for isolation | Yes conforming to IEC 60947-1 |
|---|
| Power dissipation per pole | 2.5 W |
|---|
| Mechanical durability | 100000 cycles |
|---|
| Electrical durability | 100000 cycles for AC-3 at 415 V In · 100000 cycles for AC-3e at 415 V In |
|---|
| Rated duty | Uninterrupted conforming to IEC 60947-4-1 |
|---|
| Connections - terminals | Power circuit: screw clamp terminal 2 cable(s) 1…6 mm² - solid · Power circuit: screw clamp terminal 2 cable(s) 1.5…6 mm² - flexible without cable end · Power circuit: screw clamp terminal 2 cable(s) 1…4 mm² - flexible with cable end |
|---|
| Tightening torque | 1.7 N.m - on screw clamp terminal |
|---|
| Fixing mode | 35 mm symmetrical DIN rail: clipped · Panel: screwed (with 2 x M4 screws) |
|---|
| Mounting position | Horizontal · Vertical |
|---|
| Width | 45 mm |
|---|
| Height | 89 mm |
|---|
| Depth | 97 mm |
|---|
| Colour | Dark grey |
|---|
| Standards | EN/IEC 60947-2 · EN/IEC 60947-4-1 · UL 60947-4-1 · CSA C22.2 No 60947-4-1 · IEC/EN 60335-2-40:Annex JJ · IEC/EN 60335-1:Clause 30.2 |
|---|
| Product certifications | CCC · UL · CSA · EAC · ATEX · LROS (Lloyds register of shipping) · BV · RINA · DNV-GL · UKCA |
|---|
| IK degree of protection | IK04 |
|---|
| IP degree of protection | IP20 conforming to IEC 60529 |
|---|
| Climatic withstand | conforming to IACS E10 |
|---|
| Ambient air temperature for storage | -40…80 °C |
|---|
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
|---|
| Ambient air temperature for operation | -20…60 °C |
|---|
| Mechanical robustness | Shocks: 30 Gn for 11 ms · Vibrations: 5 Gn, 5...150 Hz |
|---|
| Operating altitude | <= 2000 m |
|---|