Schneider Electric TeSys GV4 motor circuit breaker, rated 50 A. Motor circuit breaker, TeSys GV4, 3P, 50A, Icu 50kA, thermal magnetic multifunction, Everlink terminals.
Motor circuit breaker, TeSys GV4, 3P, 50A, Icu 50kA, thermal magnetic multifunction, Everlink terminals. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | TeSys Deca |
|---|
| Range of product | TeSys GV4 |
|---|
| Device short name | GV4PEM |
|---|
| Product name | TeSys GV4 |
|---|
| Product or component type | Motor circuit breaker |
|---|
| Device application | Motor protection |
|---|
| Trip unit technology | Electronic · Thermal-magnetic |
|---|
| Poles description | 3P |
|---|
| Utilisation category | Category A conforming to IEC 60947-2 · AC-3 conforming to IEC 60947-4-1 |
|---|
| Operating position | Any position |
|---|
| Motor power kW | 11 kW at 400...415 V AC 50/60 Hz · 15 kW at 500 V AC 50/60 Hz · 18.5 kW at 660...690 V AC 50/60 Hz · 15 kW at 400...415 V AC 50/60 Hz · 18.5 kW at 400...415 V AC 50/60 Hz · 22 kW at 400...415 V AC 50/60 Hz · 18.5 kW at 500 V AC 50/60 Hz · 22 kW at 500 V AC 50/60 Hz · 30 kW at 500 V AC 50/60 Hz · 22 kW at 660...690 V AC 50/60 Hz · 30 kW at 660...690 V AC 50/60 Hz · 37 kW at 660...690 V AC 50/60 Hz · 45 kW at 660...690 V AC 50/60 Hz |
|---|
| Breaking capacity | 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 · 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 · 15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 · 65 kA at 208Y/120 V AC 50/60 Hz conforming to UL 60947 · 65 kA at 240 V AC 50/60 Hz conforming to UL 60947 · 35 kA at 480Y/277 V AC 50/60 Hz conforming to UL 60947 · 8 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2 · 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 · 18 kA at 600Y/347 V AC 50/60 Hz conforming to UL 60947 |
|---|
| Control type | Toggle |
|---|
| [In] rated current | 50 A |
|---|
| Magnetic tripping current | 850 A |
|---|
| [Ue] rated operational voltage | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| [Ith] conventional free air thermal current | 115 A conforming to IEC 60947-4-1 |
|---|
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947-2 |
|---|
| Power dissipation per pole | 4.6 W |
|---|
| Mechanical durability | 40000 cycles |
|---|
| Electrical durability | 5000 cycles for AC-3 at 415 V opening · 5000 cycles for AC-3 at 440 V closing |
|---|
| maximum operating rate | 25 cyc/h |
|---|
| Rated duty | Continuous conforming to IEC 60947-4-1 |
|---|
| Connections - terminals | EverLink BTR screw connectors (top): 1 cable(s) 1.5…70 mm² - solid · EverLink BTR screw connectors (top): 1 cable(s) 1.5…50 mm² - flexible · EverLink BTR screw connectors (bottom): 1 cable(s) 2.5…95 mm² - solid · EverLink BTR screw connectors (bottom): 1 cable(s) 2.5…70 mm² - flexible |
|---|
| Tightening torque | 9 N.m for cable 16…95 mm² · 5 N.m for cable 1.5…10 mm² |
|---|
| Mechanical robustness | Vibrations: +/- 1 mm 2...13.2 Hz conforming to IEC 60068-2-6 · Vibrations: 0.7 gn 13.2...100 Hz conforming to IEC 60068-2-6 · Shocks: 15 gn 11 ms conforming to IEC 60068-2-27 |
|---|
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
|---|
| Height | 155 mm |
|---|
| Width | 81 mm |
|---|
| Depth | 116 mm |
|---|
| Product weight | 1.45 kg |
|---|
| Colour | Grey (RAL 7016) |
|---|
| Suitability for isolation | Yes conforming to IEC 60947-1 |
|---|
| Standards | CSA C22.2 No 60947-4-1 · UL 60947-4-1 · EN/IEC 60947-4-1 · EN/IEC 60947-2 |
|---|
| Product certifications | IEC · UL · CSA · CCC · EAC · ATEX · EU-RO MR |
|---|
| Climatic withstand | conforming to IACS E10 |
|---|
| IK degree of protection | IK07 conforming to IEC 62262 |
|---|
| Pollution degree | 3 |
|---|
| IP degree of protection | IP40 conforming to IEC 60529 |
|---|
| Ambient air temperature for storage | -50…85 °C |
|---|
| Fire resistance | 960 °C conforming to IEC 60695-2-11 |
|---|
| Operating altitude | 5000 m |
|---|
| Ambient air temperature for operation | -25…70 °C |
|---|
| Unit Type of Package 2 | S03 |
|---|