Schneider Electric modular timing relay. multifunction relay, Harmony Timer Relays, 8A, 1CO, 0.1s.10h, power on delay, spring terminals, 12..240V AC DC.
multifunction relay, Harmony Timer Relays, 8A, 1CO, 0.1s..10h, power on delay, spring terminals, 12...240V AC DC. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range of product | Harmony Timer Relays |
|---|
| Discrete output type | Relay |
|---|
| Product or component type | Modular timing relay |
|---|
| Width | 17.5 mm |
|---|
| Device short name | RE17R |
|---|
| Time delay type | Power on-delay · On-delay and off-delay · Interval · Off-delay · Symmetrical flashing |
|---|
| Time delay range | 6...60 min · 6...60 s · 1...10 min · 1...10 h · 0.1...1 s · 10...100 h · 1...10 s |
|---|
| nominal output current | 8 A |
|---|
| Contacts type and composition | 1 C/O |
|---|
| Contacts material | Cadmium free |
|---|
| Height | 90 mm |
|---|
| Depth | 72 mm |
|---|
| Control type | Selector switch front panel |
|---|
| [Us] rated supply voltage | 12...240 V AC/DC 50/60 Hz |
|---|
| Voltage range | 0.85...1.1 Us |
|---|
| Supply frequency | 50...60 Hz +/- 5 % |
|---|
| release of input voltage | 5 V |
|---|
| Connections - terminals | Spring terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) solid without cable end · Spring terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end |
|---|
| Housing material | Polycarbonate |
|---|
| Repeat accuracy | +/- 0.5 % conforming to IEC 61812-1 |
|---|
| Temperature drift | +/- 0.05 %/°C |
|---|
| Voltage drift | +/- 0.2 %/V |
|---|
| Setting accuracy of time delay | +/- 10 % of full scale at 25 °C conforming to IEC 61812-1 |
|---|
| control signal pulse width | 100 ms with load in parallel typical · 30 ms typical |
|---|
| Insulation resistance | 100 MOhm at 500 V DC conforming to IEC 60664-1 |
|---|
| Reset time | 120 ms on de-energisation typical |
|---|
| On-load factor | 100 % |
|---|
| Power consumption in VA | 0…3 VA at 240 V AC |
|---|
| Maximum power consumption in W | 1.5 W at 240 V DC |
|---|
| Minimum switching current | 10 mA at 5 V DC |
|---|
| Maximum switching current | 8 A AC/DC |
|---|
| Maximum switching voltage | 250 V AC |
|---|
| breaking capacity | 2000 VA |
|---|
| operating frequency | 10 Hz |
|---|
| Electrical durability | 100000 cycles (8 A at 250 V AC maximum) for resistive load |
|---|
| Mechanical durability | 10000000 cycles |
|---|
| Dielectric strength | 2.5 kV 1 mA/1 minute 50 Hz conforming to IEC 61812-1 |
|---|
| [Uimp] rated impulse withstand voltage | 5 kV during 1.2/50 µs |
|---|
| power on delay | 100 ms |
|---|
| Marking | CE |
|---|
| Creepage distance | 4 kV/3 conforming to IEC 60664-1 |
|---|
| Safety reliability data | MTTFd = 296.8 years · B10d = 270000 |
|---|
| Mounting position | Any position in relation to normal vertical mounting plane |
|---|
| Mounting support | 35 mm DIN rail conforming to IEC 60715 |
|---|
| Local signalling | LED indicator for on steady: relay energised, no timing in progress · LED indicator for flashing: timing in progress 80 % ON and 20 % OFF · LED indicator for pulsing: relay de-energised, no timing in progress (except function Di-D, Li-L) 5 % ON and 95 % OFF |
|---|