Schneider Electric ComPacT NSX circuit breaker, rated 500 A. Circuit breaker, ComPacT NSX630F, 36kA/415VAC, 3 poles, MicroLogic 1.3M trip unit 500A.
Circuit breaker, ComPacT NSX630F, 36kA/415VAC, 3 poles, MicroLogic 1.3M trip unit 500A. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | ComPacT |
|---|
| Product name | ComPacT NSX |
|---|
| Device short name | NSX630F |
|---|
| Product or component type | Circuit breaker |
|---|
| Device application | Motor protection |
|---|
| Poles description | 3P |
|---|
| Protected poles description | 3D |
|---|
| [In] rated current | 500 A at 65 °C |
|---|
| [Ue] rated operational voltage | 690 V AC 50/60 Hz |
|---|
| Network type | AC |
|---|
| Network frequency | 50/60 Hz |
|---|
| Suitability for isolation | Yes conforming to EN/IEC 60947-2 |
|---|
| Utilisation category | Category A |
|---|
| Breaking capacity | 40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 · 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 · 30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 · 25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 · 20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 · 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 · 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 · 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 · 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1 |
|---|
| Breaking capacity code | F 36 kA 415 V AC |
|---|
| Trip unit name | MicroLogic 1.3 M |
|---|
| Trip unit technology | Electronic |
|---|
| Trip unit protection functions | SI |
|---|
| Control type | Toggle |
|---|
| Circuit breaker mounting mode | Fixed |
|---|
| [Ui] rated insulation voltage | 800 V AC 50/60 Hz |
|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
|---|
| [Ics] rated service breaking capacity | 40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 · 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 · 30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 · 25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 · 10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 · 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 |
|---|
| Mechanical durability | 15000 cycles |
|---|
| Electrical durability | 8000 cycles at 440 V In/2 · 4000 cycles at 440 V In · 6000 cycles at 690 V In/2 · 2000 cycles at 690 V In |
|---|
| Power dissipation per pole | 25 W |
|---|
| Mounting support | Backplate |
|---|
| Mounting position | Horizontal and vertical · Flat on the back |
|---|
| Upside connection | Front |
|---|
| Downside connection | Front |
|---|
| Connection pitch | 45 mm |
|---|
| Protection type | S : for short time short-circuit protection · I : for instantaneous short-circuit protection |
|---|
| Trip unit rating | 500 A at 65 °C |
|---|
| Short-time protection pick-up adjustment type Isd | Adjustable 9 settings |
|---|
| [Isd] Short-time protection pick-up adjustment range | 2500 A · 3000 A · 3500 A · 4000 A · 4500 A · 5000 A · 5500 A · 6000 A · 6500 A |
|---|
| Short-time protection delay adjustment type tsd | Fixed |
|---|
| Instantaneous protection pick-up adjustment type Ii | Fixed |
|---|
| [Ii] instantaneous protection pick-up adjustment range | 6500 A |
|---|
| Earth-leakage protection | Without |
|---|
| Zone selective interlocking ZSI | Without |
|---|
| Number of slots | 6 slot(s) |
|---|
| Local signalling | Flashing LED (green) for ready to operate |
|---|
| Width (W) | 140 mm |
|---|
| Height (H) | 255 mm |
|---|
| Depth (D) | 110 mm |
|---|