Schneider Electric PowerLogic PM5000 power meter, rated 1 A. power meter PowerLogic PM5650, 2 ethernet, up to 63th Harmonic, 1,1MB, waveform, 4DI/2DO 52 alarms.
power meter PowerLogic PM5650, 2 ethernet, up to 63th Harmonic, 1,1MB, waveform, 4DI/2DO 52 alarms. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | PowerLogic |
|---|
| Product name | PowerLogic PM5000 |
|---|
| Product or component type | Power meter |
|---|
| Device short name | PM5650 |
|---|
| Power quality analysis | up to the 63rd harmonic · waveform capture · voltage sag and swell detection |
|---|
| Metering type | Measured neutral current · Calculated ground current |
|---|
| Device application | Gateway · WAGES metering · Power monitoring · Multi-tariff |
|---|
| Type of measurement | Current · Voltage · Frequency · Power factor · Energy · Active and reactive power |
|---|
| [Us] rated supply voltage | 100...300 V DC · 90...528 V AC 45...65 Hz |
|---|
| Network frequency | 60 Hz · 50 Hz |
|---|
| [In] rated current | 1 A · 5 A |
|---|
| type of network | 3P + N · 3P · 1P + N |
|---|
| Maximum power consumption in VA | 16 VA at 480 V |
|---|
| Ride-through time | 35 ms 120 V AC typical · 129 ms 230 V AC typical · 50 ms 125 V DC typical |
|---|
| Display type | Monochrome graphic LCD |
|---|
| Display resolution | 128 x 128 pixels |
|---|
| Sampling rate | 128 samples/cycle |
|---|
| Measurement current | 50…10000 mA |
|---|
| Analogue input type | Voltage (impedance 5 MOhm) · Current (impedance <= 0.3 mOhm) |
|---|
| Measurement voltage | 20…400 V AC 45...65 Hz between phase and neutral · 20…828 V AC 45...65 Hz between phases |
|---|
| Frequency measurement range | 45…65 Hz |
|---|
| Number of inputs | 4 digital |
|---|
| Measurement accuracy | Apparent power +/- 0.5 % · Frequency +/- 0.05 % · Active energy +/- 0.2 % · Reactive energy +/- 1 % · Active power +/- 0.2 % · Voltage +/- 0.1 % · Power factor +/- 0.005 · Current +/- 0.15 % · Reactive power +/- 1 % |
|---|
| Accuracy class | Class 0.2S active energy conforming to IEC 62053-22 |
|---|
| Number of outputs | 2 digital |
|---|
| Information displayed | Tariff (8) |
|---|
| Communication port protocol | Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V · JBUS · Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V · Ethernet Modbus TCP/IP daisy chain · BACnet IP · DNP3 over ethernet |
|---|
| Communication port support | RS485 · ETHERNET |
|---|
| Communication gateway | Ethernet/serial |
|---|
| Data recording | Event logs · Maintenance logs · Min/max of instantaneous values · Data logs · Alarm logs · Time stamping |
|---|
| Memory capacity | 1.1 MB |
|---|
| Web services | Alarm notification by e-mail · Web server · Diagnostic via predefined web pages · Real time viewing of data |
|---|
| Ethernet service | SNTP client · SNMP-Traps |
|---|
| Connections - terminals | Voltage circuit: screw terminal block4 · Control circuit: screw terminal block2 · Current transformer: screw terminal block6 · RS485 link: screw terminal block4 · Digital input: screw terminal block8 · Digital output: screw terminal block4 · Ethernet network: RJ45 connector2 |
|---|
| Mounting mode | Flush-mounted |
|---|
| Mounting support | Framework |
|---|
| Standards | EN 50470-3 · IEC 61557-12:2015 · IEC 62053-22:2020 · IEC 62053-24 · IEC 60529 · EN 50470-1 · UL 61010-1 · IEC 62053-23:2020 · IEC 62052-11:2020 · IEC 62052-31:2015 |
|---|
| Product certifications | CE conforming to IEC 61010-1 · CULus conforming to UL 61010-1 |
|---|
| Width | 96 mm |
|---|
| Depth | 72 mm |
|---|
| Height | 96 mm |
|---|
| Product weight | 450 g |
|---|
| Electromagnetic compatibility | Limits for harmonic current emissions class A conforming to IEC 61000-3-2 · Conducted RF disturbances level 3 conforming to IEC 61000-4-6 · Magnetic field at power frequency level 4 conforming to IEC 61000-4-8 · Conducted and radiated emissions class B conforming to EN 55022 · Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3 · Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2 · Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 · Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 · Surge immunity test level 4 conforming to IEC 61000-4-5 · Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 |
|---|
| IP degree of protection | IP54 display: conforming to IEC 60529 · IP30 rear: conforming to IEC 60529 |
|---|
| Relative humidity | 5…95 % at 50 °C non-condensing |
|---|