- Range
- PowerLogic
- Range
- PowerLogic
- Range
- PowerLogic
- Product name
- PowerLogic PM5000
- Product name
- PowerLogic PM5000
- Product name
- PowerLogic PM5000
- type of network
- 3P · 1P + N · 3P + N
- Ride-through time
- 100 ms 120 V AC typical · 400 ms 230 V AC typical · 50 ms 125 V DC typical
- Display type
- Monochrome graphic LCD
- Display resolution
- 128 x 128 pixels
- Sampling rate
- 64 samples/cycle
- Analogue input type
- Voltage (impedance 10 MOhm) · Current (impedance <= 0.3 mOhm)
- Number of inputs
- 2 digital
- Measurement accuracy
- Active energy +/- 0.5 % · Reactive energy +/- 2 % · Active power +/- 0.5 % · Apparent power +/- 0.5 % · Frequency +/- 0.05 % · Power factor +/- 0.5 · Current +/- 0.5 % · Voltage +/- 0.5 % · Apparent energy +/- 0.5 % · Reactive power +/- 2 %
- Accuracy class
- Class 0.5S active energy conforming to IEC 62053-22
- Number of outputs
- 2 relay · 2 digital
- Information displayed
- Tariff (4)
- Communication port protocol
- Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V · BACnet IP
- Communication port protocol
- Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V · BACnet IP
- Communication port support
- ETHERNET
- Data recording
- Data logs · Alarm logs · Time stamping · Event logs · Min/max of instantaneous values · Maintenance logs
- Connections - terminals
- Voltage circuit: screw terminal block4 · Control circuit: screw terminal block2 · Current transformer: screw terminal block6 · Input/output circuit: screw terminal block6 · Relay output: screw terminal block4 · Ethernet network: RJ45 connector
- Connections - terminals
- Voltage circuit: screw terminal block4 · Control circuit: screw terminal block2 · Current transformer: screw terminal block6 · Input/output circuit: screw terminal block6 · Relay output: screw terminal block4 · Ethernet network: RJ45 connector
- Electromagnetic compatibility
- Limits for harmonic current emissions class A conforming to IEC 61000-3-2 · Electrostatic discharge level 4 conforming to IEC 61000-4-2 · Conducted RF disturbances level 3 conforming to IEC 61000-4-6 · Magnetic field at power frequency level 4 conforming to IEC 61000-4-8 · Conducted and radiated emissions class B conforming to EN 55022
- IP degree of protection
- IP51 display: conforming to IEC 60529 · IP30 rear: conforming to IEC 60529
- Pollution degree
- 2