- Range
- PowerLogic
- Range
- PowerLogic
- Range
- PowerLogic
- Product name
- PowerLogic PM5000
- Product name
- PowerLogic PM5000
- Type of measurement
- Current · Voltage · Frequency · Power factor · Energy · Active and reactive power
- type of network
- 3P + N · 3P · 1P + N
- Ride-through time
- 35 ms 120 V AC typical · 129 ms 230 V AC typical · 50 ms 125 V DC typical
- Display resolution
- 128 x 128 pixels
- Sampling rate
- 128 samples/cycle
- Number of inputs
- 4 digital
- Measurement accuracy
- Apparent power +/- 0.5 % · Frequency +/- 0.05 % · Active energy +/- 0.2 % · Reactive energy +/- 1 % · Active power +/- 0.2 % · Voltage +/- 0.1 % · Power factor +/- 0.005 · Current +/- 0.15 % · Reactive power +/- 1 %
- Measurement accuracy
- Apparent power +/- 0.5 % · Frequency +/- 0.05 % · Active energy +/- 0.2 % · Reactive energy +/- 1 % · Active power +/- 0.2 % · Voltage +/- 0.1 % · Power factor +/- 0.005 · Current +/- 0.15 % · Reactive power +/- 1 %
- Accuracy class
- Class 0.2S active energy conforming to IEC 62053-22
- Number of outputs
- 2 digital
- Number of outputs
- 2 digital
- Information displayed
- Tariff (8)
- Information displayed
- Tariff (8)
- Information displayed
- Tariff (8)
- Communication port protocol
- Modbus RTU and ASCII at 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires, insulation 2500 V · JBUS · Modbus TCP/IP at 10/100 Mbit/s, insulation 2500 V · Ethernet Modbus TCP/IP daisy chain · BACnet IP · DNP3 over ethernet
- Communication gateway
- Ethernet/serial
- Data recording
- Event logs · Maintenance logs · Min/max of instantaneous values · Data logs · Alarm logs · Time stamping
- Memory capacity
- 1.1 MB
- Web services
- Alarm notification by e-mail · Diagnostic via predefined web pages · Web server · Real time viewing of data
- Connections - terminals
- Voltage circuit: screw terminal block4 · Control circuit: screw terminal block2 · Current transformer: screw terminal block6 · RS485 link: screw terminal block4 · Digital input: screw terminal block8 · Digital output: screw terminal block4 · Ethernet network: RJ45 connector2
- Electromagnetic compatibility
- Limits for harmonic current emissions class A conforming to IEC 61000-3-2 · Conducted RF disturbances level 3 conforming to IEC 61000-4-6 · Magnetic field at power frequency level 4 conforming to IEC 61000-4-8 · Conducted and radiated emissions class B conforming to EN 55022 · Limitation of voltage changes, voltage fluctuations and flicker in low-voltage conforming to IEC 61000-3-3 · Electrostatic discharge - test level: 8 kV level 4 conforming to IEC 61000-4-2 · Radiated radio-frequency electromagnetic field immunity test conforming to IEC 61000-4-3 · Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 · Surge immunity test level 4 conforming to IEC 61000-4-5 · Voltage dips and interruptions immunity test conforming to IEC 61000-4-11
- IP degree of protection
- IP54 display: conforming to IEC 60529 · IP30 rear: conforming to IEC 60529