Schneider Electric CT current transformer, rated 1000 A. PowerLogic Split Core Current Transformer - Type GJ, for bar - 1000A / 5A.
PowerLogic Split Core Current Transformer - Type GJ, for bar - 1000A / 5A. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range | PowerLogic |
|---|
| Product or component type | Current transformer |
|---|
| Product name | CT |
|---|
| Secondary current | 5 A |
|---|
| Accuracy class | Class 0.5 at 10 VA |
|---|
| [In] rated current | 1000 A |
|---|
| Current transformer type | Standard for busbar · Split core |
|---|
| Current transformer ratio | 1000/5 |
|---|
| [Ith] conventional free air thermal current | 1000 A |
|---|
| Maximum safety factor | 5 |
|---|
| Permissible current | 60000 A during 1 s |
|---|
| [Ue] rated operational voltage | < 720 V 50 Hz |
|---|
| [Ui] rated insulation voltage | 3 kV 50 Hz for 1 minute |
|---|
| Mounting mode | By screws |
|---|
| Mounting support | DIN rail · Fastened onto a surface with screws |
|---|
| Width | Outside: 195 mm · Inner: 85 mm |
|---|
| Height | Outside: 243 mm · Inner: 165 mm |
|---|
| Depth | 79 mm |
|---|
| Electrical insulation class | Class E |
|---|
| Opening of bars | 85 x 165 |
|---|
| Standards | VDE 0414 · DIN 42600-2 · DIN EN 61869-1 · DIN EN 61869-2 |
|---|
| Ambient air temperature for operation | -5…40 °C |
|---|
| Ambient air temperature for storage | -25…70 °C |
|---|
| Unit Type of Package 2 | S03 |
|---|
| Number of Units in Package 2 | 4 |
|---|
| Package 2 Height | 30.0 cm |
|---|
| Package 2 Width | 30.0 cm |
|---|
| Package 2 Length | 40.0 cm |
|---|
| Package 2 Weight | 12.988 kg |
|---|
| Warranty (in months) | 18 |
|---|