Technical specifications
| Range | TeSys |
|---|
| Device short name | LU6MB |
|---|
| Product or component type | Reverser block |
|---|
| Device mounting | Separate mounting |
|---|
| Device application | Motor control |
|---|
| [Ie] rated operational current | 32 A |
|---|
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
|---|
| Current consumption | 2360 mA at 24 V AC I maximum while closing |
|---|
| [Ue] rated operational voltage | 690 V AC power circuit |
|---|
| Network frequency | 40...60 Hz |
|---|
| Inrush restraint duration | 25 ms AC · 15 ms DC |
|---|
| Operating time | 150 ms with change of direction · 75 ms without change of direction |
|---|
| Standards | EN 60947-6-2 · IEC 60947-6-2 · UL 60947-4-1, with phase barrier · CSA C22.2 No 60947-4-1, with phase barrier |
|---|
| Product certifications | CE · UL · CSA · CCC · EAC · ASEFA · ATEX · Marine |
|---|
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947-6-2 · 600 V conforming to UL 60947-4-1 · 600 V conforming to CSA C22.2 No 60947-4-1 |
|---|
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-6-2 |
|---|
| Fixing mode | Clipped (DIN rail) · Screw-fixed (plate) |
|---|
| Connections - terminals | Control circuit: screw clamp terminals 1 cable(s) 0.34…1.5 mm² (external diameter: 3 mm) flexible with cable end · Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) flexible without cable end · Control circuit: screw clamp terminals 1 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) rigid · Control circuit: screw clamp terminals 2 cable(s) 0.34…1.5 mm² (external diameter: 3 mm) flexible with cable end · Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) flexible without cable end · Control circuit: screw clamp terminals 2 cable(s) 0.75…1.5 mm² (external diameter: 3 mm) rigid · Power circuit: screw clamp terminals 1 cable(s) 1…10 mm² (external diameter: 4 mm) rigid · Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² (external diameter: 4 mm) flexible with cable end · Power circuit: screw clamp terminals 1 cable(s) 2.5…10 mm² (external diameter: 4 mm) flexible without cable end · Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² (external diameter: 4 mm) flexible with cable end · Power circuit: screw clamp terminals 2 cable(s) 1…6 mm² (external diameter: 4 mm) rigid · Power circuit: screw clamp terminals 2 cable(s) 1.5…6 mm² (external diameter: 4 mm) flexible without cable end |
|---|
| Tightening torque | Control circuit: 0.8…1.2 N.m flat screwdriver 5 mm · Control circuit: 0.8…1.2 N.m Philips No 2 screwdriver 5 mm · Power circuit: 1.9…2.5 N.m flat screwdriver 6 mm · Power circuit: 1.9…2.5 N.m Philips No 2 screwdriver 6 mm · Power circuit: 1.9…2.5 N.m pozidriv No 2 screwdriver 6 mm |
|---|
| Width | 45 mm |
|---|
| Height | 115 mm |
|---|
| Depth | 113 mm |
|---|
| Product weight | 0.425 kg |
|---|
| Compatibility code | LU6MB |
|---|
| IP degree of protection | IP20 conforming to IEC 60947-1 (front panel and wired terminals) · IP20 conforming to IEC 60947-1 (other faces) · IP40 conforming to IEC 60947-1 (front panel outside connection zone) |
|---|
| Protective treatment | TH conforming to IEC 60068 |
|---|
| Ambient air temperature for operation | -25…60 °C with LUCM · -25…70 °C with LUCA, LUCB, LUCC, LUCD |
|---|
| Ambient air temperature for storage | -40…85 °C |
|---|
| Fire resistance | 960 °C parts supporting live components conforming to IEC 60695-2-12 · 650 °C conforming to IEC 60695-2-12 |
|---|
| Operating altitude | 2000 m |
|---|
| Shock resistance | 10 gn power poles open conforming to IEC 60068-2-27 · 15 gn power poles closed conforming to IEC 60068-2-27 |
|---|
| Vibration resistance | 2 gn (f= 5…300 Hz) power poles open conforming to IEC 60068-2-27 · 4 gn (f= 5…300 Hz) power poles closed conforming to IEC 60068-2-27 |
|---|
| Resistance to electrostatic discharge | 8 kV level 3, in open air conforming to IEC 61000-4-2 · 8 kV level 4, on contact conforming to IEC 61000-4-2 |
|---|
| Resistance to radiated fields | 10 V/m level 3 conforming to IEC 61000-4-3 |
|---|
| Resistance to fast transients | 2 kV class 3 serial link conforming to IEC 61000-4-4 · 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4 |
|---|
| Non-dissipating shock wave | 1 kV serial mode conforming to IEC 60947-6-2 · 2 kV common mode conforming to IEC 60947-6-2 |
|---|
| Immunity to radioelectric fields | 10 V conforming to IEC 61000-4-6 |
|---|
| Unit Type of Package 2 | S02 |
|---|
| Number of Units in Package 2 | 10 |
|---|
| Package 2 Height | 15.0 cm |
|---|
| Package 2 Width | 30.0 cm |
|---|
| Package 2 Length | 40.0 cm |
|---|
| Package 2 Weight | 4.632 kg |
|---|
| Warranty (in months) | 18 |
|---|