Schneider Electric elevator machine room temperature control relay. temperature control relay, Harmony Control Relays, 5A, 1CO, 24.240V AC DC.
temperature control relay, Harmony Control Relays, 5A, 1CO, 24..240V AC DC. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range of product | Harmony Control Relays |
|---|
| Relay type | Temperature control relays |
|---|
| Product or component type | Elevator machine room temperature control relay |
|---|
| Product specific application | For elevator machine rooms and 3-phase supplies |
|---|
| Relay name | RM35AT |
|---|
| Relay monitored parameters | Under temperature: -1...11°C · Over temperature: 34...46°C |
|---|
| Time delay range | 0.1...10 s adjustable delay (tolerance: 0...10 % of the full scale value) |
|---|
| Switching capacity in VA | 1250 VA |
|---|
| Minimum switching current | 10 mA at 5 V DC |
|---|
| Maximum power consumption in VA | 3.5 VA AC |
|---|
| Utilisation category | AC-12 conforming to IEC 60947-5-1 · AC-13 conforming to IEC 60947-5-1 · AC-14 conforming to IEC 60947-5-1 · AC-15 conforming to IEC 60947-5-1 · DC-12 conforming to IEC 60947-5-1 · DC-13 conforming to IEC 60947-5-1 · DC-14 conforming to IEC 60947-5-1 |
|---|
| time delay | Adjustable 1...10 s Tt- time delay upon fault |
|---|
| Measurement range | +/- 1...46 °C |
|---|
| Reset time | 8 s |
|---|
| Maximum switching voltage | 250 V AC/DC |
|---|
| [Us] rated supply voltage | 24...240 V AC/DC |
|---|
| [Un] rated nominal voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
|---|
| Supply voltage limits | 20.4…264 V AC · 21.6…264 V DC |
|---|
| Maximum power consumption in W | 0.6 W DC |
|---|
| Resistance across terminals | 1.33 kOhm at temperature |
|---|
| Width | 35 mm |
|---|
| Output contacts | 1 C/O |
|---|
| Contacts material | Cadmium free |
|---|
| nominal output current | 5 A |
|---|
| delay at power up | 0.2 s |
|---|
| Measurement accuracy | +/- 2 °C |
|---|
| Response time | <= 3.5 s + Tt (in case of temperature fault) · <= 3.5 s (on disappearance of fault) |
|---|
| Temperature probe type | Pt 100 - 3-wire |
|---|
| Installed device | Pt 100 probe cable length <= 10 m |
|---|
| Marking | CE : EMC 89/336/EEC · CE : 73/23/EEC |
|---|
| Overvoltage category | III conforming to IEC 60664-1 |
|---|
| Insulation resistance | > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60255-5 · > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60664-1 · > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60255-5 · > 500 MOhm at 500 V DC between supply and relay output conforming to IEC 60664-1 · > 500 MOhm at 500 V DC between measurement and relay output conforming to IEC 60255-5 · > 1 MOhm at 500 V DC between supply and measurement conforming to IEC 60664-1 |
|---|
| [Ui] rated insulation voltage | 250 V conforming to IEC 60664-1 |
|---|
| operating voltage tolerance | - 10 % + 10 % Un DC · - 15 % + 10 % Un AC |
|---|
| Supply frequency | 50/60 Hz +/- 10 % |
|---|
| Insulation | Galvanic insulation between supply and measurement |
|---|
| Operating position | Any position without derating |
|---|
| Connections - terminals | Screw terminals, 1 x 0.5...1 x 4 mm² (20 AWG...11 AWG) solid without cable end · Screw terminals, 2 x 0.5...2 x 2.5 mm² (20 AWG...14 AWG) solid without cable end · Screw terminals, 1 x 0.2...1 x 2.5 mm² (24 AWG...12 AWG) flexible with cable end · Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) flexible with cable end |
|---|
| Tightening torque | 0.6…1 N.m conforming to IEC 60947-1 |
|---|
| Housing material | Polycarbonate |
|---|
| local signalling | 1 LED green for power ON · 1 LED yellow for correct temperature (high R1) · 1 LED yellow for correct temperature (low R2) |
|---|
| Mounting support | 35 mm symmetrical DIN rail conforming to IEC 60715 |
|---|
| Electrical durability | 100000 cycles |
|---|
| Mechanical durability | 30000000 cycles |
|---|
| Operating rate | <= 360 operations/hour full load |
|---|