| Range of product | Zelio Logic |
|---|
| Product or component type | Compact smart relay |
|---|
| Local display | With |
|---|
| Number or control scheme lines | 0…240 with ladder programming |
|---|
| Cycle time | 6…90 ms |
|---|
| Backup time | 10 years at 25 °C |
|---|
| Clock drift | 12 min/year at 0…55 °C · 6 s/month at 25 °C |
|---|
| Checks | Program memory on each power up |
|---|
| [Us] rated supply voltage | 24 V DC |
|---|
| Supply voltage limits | 19.2…30 V |
|---|
| Maximum supply current | 100 mA (without extension) |
|---|
| Power dissipation in W | 3 W without extension |
|---|
| Reverse polarity protection | With |
|---|
| Discrete input number | 6 conforming to IEC 61131-2 Type 1 |
|---|
| Discrete input type | Resistive |
|---|
| Discrete input voltage | 24 V DC |
|---|
| Discrete input current | 4 mA |
|---|
| Counting frequency | 1 kHz for discrete input |
|---|
| Voltage state 1 guaranteed | >= 15 V for I1...IA and IH...IR discrete input circuit · >= 15 V for IB...IG used as discrete input circuit |
|---|
| Voltage state 0 guaranteed | <= 5 V for I1...IA and IH...IR discrete input circuit · <= 5 V for IB...IG used as discrete input circuit |
|---|
| Current state 1 guaranteed | >= 1.2 mA (IB...IG used as discrete input circuit) · >= 2.2 mA (I1...IA and IH...IR discrete input circuit) |
|---|
| Current state 0 guaranteed | <= 0.5 mA (IB...IG used as discrete input circuit) · <= 0.75 mA (I1...IA and IH...IR discrete input circuit) |
|---|
| Input compatibility | 3-wire proximity sensors PNP for discrete input |
|---|
| Analogue input number | 0 |
|---|
| Input impedance | 12 kOhm for IB...IG used as analogue input circuit · 12 kOhm for IB...IG used as discrete input circuit · 7.4 kOhm for I1...IA and IH...IR discrete input circuit |
|---|
| Number of outputs | 4 relay |
|---|
| Output voltage limits | 24...250 V AC (relay output) · 5...30 V DC (relay output) |
|---|
| Contacts type and composition | NO for relay output |
|---|
| Output thermal current | 8 A for all 4 outputs for relay output |
|---|
| Electrical durability | AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to IEC 60947-5-1 · AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to IEC 60947-5-1 · DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to IEC 60947-5-1 · DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to IEC 60947-5-1 |
|---|
| Switching capacity in mA | >= 10 mA at 12 V (relay output) |
|---|
| Operating rate in Hz | 0.1 Hz (at Ie) for relay output · 10 Hz (no load) for relay output |
|---|
| Mechanical durability | 10000000 cycles for relay output |
|---|
| [Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1 |
|---|
| Clock | Without |
|---|
| Response time | 10 ms (from state 0 to state 1) for relay output · 5 ms (from state 1 to state 0) for relay output |
|---|
| Connections - terminals | Screw terminals, 1 x 0.2...1 x 2.5 mm² (25 AWG...14 AWG) semi-solid · Screw terminals, 1 x 0.2...1 x 2.5 mm² (25 AWG...14 AWG) solid · Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end · Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) solid · Screw terminals, 2 x 0.25...2 x 0.75 mm² (24 AWG...18 AWG) flexible with cable end |
|---|
| Tightening torque | 0.5 N.m |
|---|
| Overvoltage category | III conforming to IEC 60664-1 |
|---|
| Product weight | 0.25 kg |
|---|
| Immunity to microbreaks | 1 ms |
|---|
| Product certifications | CSA · UL · C-Tick · GL · GOST |
|---|
| Standards | IEC 61000-4-4 level 3 · IEC 60068-2-27 Ea · IEC 61000-4-3 · IEC 61000-4-11 · IEC 61000-4-12 · IEC 60068-2-6 Fc · IEC 61000-4-6 level 3 · IEC 61000-4-5 · IEC 61000-4-2 level 3 |
|---|
| IP degree of protection | IP20 (terminal block) conforming to IEC 60529 · IP40 (front panel) conforming to IEC 60529 |
|---|
| Environmental characteristic | EMC directive conforming to IEC 61000-6-2 · EMC directive conforming to IEC 61000-6-3 · EMC directive conforming to IEC 61000-6-4 · EMC directive conforming to IEC 61131-2 zone B · Low voltage directive conforming to IEC 61131-2 |
|---|