| Range of product | Altivar Soft Starter ATS490 |
|---|
| Product or component type | Soft starter |
|---|
| Product destination | Asynchronous motors |
|---|
| Product specific application | Process and infrastructures |
|---|
| Device short name | ATS490 |
|---|
| Network number of phases | 3 phases |
|---|
| Utilisation category | AC-3A · AC-53A |
|---|
| Ue power supply voltage | 208...690 V AC (- 15...10 %) |
|---|
| power supply frequency | 50...60 Hz - 20...20 % |
|---|
| [Ie] rated operational current | Normal duty: 17 A in line (at <40 °C) |
|---|
| Service factor at Ie | 100 |
|---|
| rated current in heavy duty | 12 A at 40 °C for heavy duty |
|---|
| Torque control | True |
|---|
| IP degree of protection | IP20 |
|---|
| Motor power kW | 4 kW at 230 V in the motor supply line normal duty · 7.5 kW at 400 V in the motor supply line normal duty · 7.5 kW at 440 V in the motor supply line normal duty · 9 kW at 500 V in the motor supply line normal duty · 9 kW at 525 V in the motor supply line normal duty · 11 kW at 660 V in the motor supply line normal duty · 15 kW at 690 V in the motor supply line normal duty · 3 kW at 230 V in the motor supply line heavy duty · 5.5 kW at 400 V in the motor supply line heavy duty · 5.5 kW at 440 V in the motor supply line heavy duty · 7.5 kW at 500 V in the motor supply line heavy duty · 7.5 kW at 525 V in the motor supply line heavy duty · 9 kW at 660 V in the motor supply line heavy duty · 11 kW at 690 V in the motor supply line heavy duty · 7.5 kW at 230 V to the motor delta terminals normal duty · 15 kW at 400 V to the motor delta terminals normal duty · 5.5 kW at 230 V to the motor delta terminals heavy duty · 11 kW at 400 V to the motor delta terminals heavy duty |
|---|
| Motor power hp | 3 hp at 208 V normal duty · 5 hp at 230 V normal duty · 10 hp at 460 V normal duty · 15 hp at 575 V normal duty · 2 hp at 208 V heavy duty · 3 hp at 230 V heavy duty · 7.5 hp at 460 V heavy duty · 10 hp at 575 V heavy duty |
|---|
| With safety function Safe torque off (STO) | True |
|---|
| Safe Torque Off (STO) | STO (safe torque off): SIL 1 conforming to IEC 61508 · STO (safe torque off): PL c/category 2 conforming to ISO 13849 |
|---|
| Cybersecurity functions | True |
|---|
| Cybersecurity level and standard | Security level (SL) 1 conforming to IEC 62443-4-2 |
|---|
| Communication port protocol | Modbus serial · Modbus TCP/EtherNet/IP |
|---|
| Option card | Communication module for CANopen daisy chain · Communication module for CANopen Sub-D · Communication module for CANopen open style · Communication module for Profibus DP V1 · Communication module for PROFINET |
|---|
| Device connection | In the motor supply line · Inside delta |
|---|
| Overload current profile | 400 % Ie for 13 s |
|---|
| On-load factor | 50 % |
|---|
| Operating cycles/hour | 10 cyc/h |
|---|
| [Us] control circuit voltage | 110...230 V AC 50...60 Hz - 15...10 % |
|---|
| Apparent power | 70 VA |
|---|
| Integrated motor overload protection | True |
|---|
| motor thermal protection class | Class 10E |
|---|
| Protection type | Phase failure: mains · Thermal protection: starter · Thermal protection: motor · Current overload: motor · Motor underload: motor · Excessive acceleration time: motor · Motor phase loss detection: motor · Protection against line phase inversion: mains · External thermal protection: motor · Protection delta inside wiring: starter · Short-circuit between motor phase and earth: motor |
|---|
| current limiting %In (5 x Ie maximum) | 150…700 % |
|---|
| Rated current pwr loss specification | 17 A |
|---|
| Power loss static current independent | 19 W |
|---|
| Power loss per device current dependent | 2 W |
|---|
| Power loss during starting | 202 W during starting at 40 °C at 400% Ie |
|---|
| Standards | EN/IEC 60947-4-2 · UL 60947-4-2 · IEC 60664-1 |
|---|
| Product certifications | CE · cULus · UKCA · RCM · CCC · DNV · ATEX · EAC · KC |
|---|
| Marking | CE · CULus · UKCA · RCM · CCC · ATEX · EAC · KC |
|---|
| [Uc] control circuit voltage | 24 V DC |
|---|
| Discrete input number | 5 |
|---|
| Discrete input type | (DI1) digital input, 4.4 kOhm · (DI2) digital input, 4.4 kOhm · (DI3) digital input, 4.4 kOhm · (DI4) digital input, 4.4 kOhm · (STO) digital input, > 1 kOhm |
|---|
| Input compatibility | DI1: discrete input level 1 PLC conforming to EN/IEC 61131-2 · DI2: discrete input level 1 PLC conforming to EN/IEC 61131-2 · DI3: discrete input level 1 PLC conforming to EN/IEC 61131-2 · DI4: discrete input level 1 PLC conforming to EN/IEC 61131-2 · STO: discrete input level 1 PLC conforming to EN/IEC 61131-2 |
|---|
| Discrete input logic | Digital input DI1 at State 0: 0... 11 V, >= 5 mA · Digital input DI2 at State 0: 0... 11 V, >= 5 mA · Digital input DI3 at State 0: 0... 11 V, >= 5 mA · Digital input DI4 at State 0: 0... 11 V, >= 5 mA · Digital input STO at State 0: 0... 11 V, >= 5 mA |
|---|
| Relay output number | 3 |
|---|