| Range of product | Zelio Logic |
|---|
| Product or component type | Discrete I/O extension module |
|---|
| Number or control scheme lines | 120 with ladder programming |
|---|
| Cycle time | 6…90 ms |
|---|
| Backup time | 10 years at 25 °C |
|---|
| Clock drift | 12 min/year at 0…55 °C |
|---|
| Checks | Program memory on each power up |
|---|
| [Us] rated supply voltage | 100...240 V AC |
|---|
| Supply voltage limits | 85…264 V |
|---|
| Supply frequency | 50/60 Hz |
|---|
| Reverse polarity protection | With |
|---|
| Discrete input number | 8 |
|---|
| Discrete input voltage | 100...240 V AC |
|---|
| Discrete input current | 0.6 mA |
|---|
| Discrete input frequency | 57...63 Hz · 47...53 Hz |
|---|
| Voltage state 1 guaranteed | >= 79 V for discrete input |
|---|
| Voltage state 0 guaranteed | <= 40 V for discrete input |
|---|
| Current state 1 guaranteed | >= 0.17 mA (discrete input) |
|---|
| Current state 0 guaranteed | <= 0.5 mA (discrete input) |
|---|
| Input impedance | 350 kOhm for discrete input |
|---|
| Number of outputs | 6 relay |
|---|
| Output voltage limits | 5...30 V DC (relay output) · 24...250 V AC |
|---|
| Contacts type and composition | NO for relay output |
|---|
| Output thermal current | 5 A for 2 outputs for relay output · 8 A for 4 outputs for relay output |
|---|
| Electrical durability | AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to IEC 60947-5-1 · AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to IEC 60947-5-1 · DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to IEC 60947-5-1 · DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to IEC 60947-5-1 |
|---|
| Switching capacity in mA | >= 10 mA at 12 V (relay output) |
|---|
| Operating rate in Hz | 0.1 Hz (at Ie) for relay output · 10 Hz (no load) for relay output |
|---|
| Mechanical durability | 10000000 cycles for relay output |
|---|
| [Uimp] rated impulse withstand voltage | 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1 |
|---|
| Response time | 50 ms with ladder programming (from state 0 to state 1) for discrete input · 50 ms with ladder programming (from state 1 to state 0) for discrete input · 50...255 ms with FBD programming (from state 0 to state 1) for discrete input · 50...255 ms with FBD programming (from state 1 to state 0) for discrete input · 10 ms (from state 0 to state 1) for relay output · 5 ms (from state 1 to state 0) for relay output |
|---|
| Connections - terminals | Screw terminals, 1 x 0.25...1 x 2.5 mm² (24 AWG...14 AWG) flexible with cable end · Screw terminals, 2 x 0.25...2 x 0.75 mm² (24 AWG...18 AWG) flexible with cable end · Screw terminals, 1 x 0.2...1 x 2.5 mm² (25 AWG...14 AWG) semi-solid · Screw terminals, 1 x 0.2...1 x 2.5 mm² (25 AWG...14 AWG) solid · Screw terminals, 2 x 0.2...2 x 1.5 mm² (24 AWG...16 AWG) solid |
|---|
| Tightening torque | 0.5 N.m |
|---|
| Overvoltage category | III conforming to IEC 60664-1 |
|---|
| Product weight | 0.22 kg |
|---|
| Product certifications | C-Tick · GOST · CSA · GL · UL |
|---|
| Standards | IEC 61000-4-6 level 3 · IEC 61000-4-2 level 3 · IEC 61000-4-4 level 3 · IEC 60068-2-27 Ea · IEC 61000-4-5 · IEC 61000-4-11 · IEC 60068-2-6 Fc · IEC 61000-4-12 · IEC 61000-4-3 |
|---|
| IP degree of protection | IP20 (terminal block) conforming to IEC 60529 · IP40 (front panel) conforming to IEC 60529 |
|---|
| Environmental characteristic | EMC directive conforming to IEC 61000-6-2 · EMC directive conforming to IEC 61000-6-3 · EMC directive conforming to IEC 61000-6-4 · EMC directive conforming to IEC 61131-2 zone B · Low voltage directive conforming to IEC 61131-2 |
|---|
| Disturbance radiated/conducted | Class B conforming to EN 55022-11 group 1 |
|---|
| Pollution degree | 2 conforming to IEC 61131-2 |
|---|
| Ambient air temperature for operation | -20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2 · -20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2 |
|---|
| Ambient air temperature for storage | -40…70 °C |
|---|
| Operating altitude | 2000 m |
|---|
| Maximum altitude transport | 3048 m |
|---|
| Relative humidity | 95 % without condensation or dripping water |
|---|