Schneider Electric standard power distribution kit. power distribution kit, Modicon STB, standard, 24V DC.
power distribution kit, Modicon STB, standard, 24V DC. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Range of product | Modicon STB distributed I/O solution |
|---|
| Product or component type | Standard power distribution kit |
|---|
| Kit composition | STBXTS2130, spring type connectors · STBPDT3100 module · STBXBA2200 base · STBXTS1130, screw type connectors |
|---|
| Product compatibility | Mounting base STBXBA2200 |
|---|
| [Us] rated supply voltage | 24 V for DC |
|---|
| Power supply output current | 10 A for input/output circuit · 12 A for input/output circuit · 6 A for input/output circuit · 8 A for input/output circuit · 0…4 A for input circuit · 0…8 A for output circuit |
|---|
| Voltage range | 19.2...30 V DC sensor/actuator bus |
|---|
| Protection type | Built-in overcurrent protection, 10 A time-lag fuse for output circuit · Built-in overcurrent protection, 5 A time-lag fuse for input circuit · Reverse polarity for actuator bus |
|---|
| Permissible current | 30 A for 2 minutes grounding terminal |
|---|
| Hot swapping fallback | No |
|---|
| Local signalling | 1 LED green for actuator bus power supply (OUT) · 1 LED green for sensor bus power supply (IN) |
|---|
| Housing colour | White |
|---|
| Height | 125 mm |
|---|
| Width | 18.4 mm |
|---|
| Depth | 65.1 mm |
|---|
| Product weight | 0.13 kg |
|---|
| Overvoltage category | II |
|---|
| IP degree of protection | IP20 |
|---|
| Marking | CE |
|---|
| Product certifications | CSA · FM Class 1 Division 2 · UL |
|---|
| Standards | EN/IEC 61131-2 type 1 |
|---|
| Ambient air temperature for operation | 0…60 °C (without derating) |
|---|
| Ambient air temperature for storage | -40…85 °C without derating |
|---|
| Relative humidity | 95 % at 60 °C without condensation |
|---|
| Operating altitude | <= 2000 m |
|---|
| Pollution degree | 2 |
|---|
| Vibration resistance | 3 gn (f = 58…150 Hz) on 35 mm DIN rail · 5 gn (f = 58…150 Hz) on 35 mm DIN rail · +/-0.35 mm (f = 10…58 Hz) |
|---|
| Shock resistance | 30 gn for 11 ms conforming to IEC 88 reference 2-27 |
|---|
| Unit Type of Package 2 | S02 |
|---|
| Number of Units in Package 2 | 24 |
|---|
| Package 2 Height | 15 cm |
|---|
| Package 2 Width | 30 cm |
|---|
| Package 2 Length | 40 cm |
|---|
| Package 2 Weight | 4.026 kg |
|---|
| Unit Type of Package 3 | P06 |
|---|
| Number of Units in Package 3 | 384 |
|---|
| Package 3 Height | 75.0 cm |
|---|
| Package 3 Width | 60.0 cm |
|---|
| Package 3 Length | 80.0 cm |
|---|
| Package 3 Weight | 75.52 kg |
|---|
| Warranty (in months) | 18 |
|---|