| Range of product | TeSys Deca |
|---|
| Product or component type | Contactor |
|---|
| Device short name | LC1D |
|---|
| Contactor application | Resistive load · Motor control |
|---|
| Utilisation category | AC-1 · AC-3 · AC-4 · AC-3e |
|---|
| Poles description | 3P |
|---|
| [Ue] rated operational voltage | Power circuit: <= 690 V AC 25...400 Hz · Power circuit: <= 300 V DC |
|---|
| [Ie] rated operational current | 9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit · 20 A (at <60 °C) at <= 440 V AC AC-1 for power circuit · 9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
|---|
| [Uc] control circuit voltage | 24 V DC |
|---|
| Motor power kW | 2.2 kW at 220...230 V AC 50/60 Hz (AC-3) · 4 kW at 380...400 V AC 50/60 Hz (AC-3) · 4 kW at 415 V AC 50/60 Hz (AC-3) · 4 kW at 440 V AC 50/60 Hz (AC-3) · 5.5 kW at 500 V AC 50/60 Hz (AC-3) · 5.5 kW at 660...690 V AC 50/60 Hz (AC-3) · 2.2 kW at 220...230 V AC 50/60 Hz (AC-3e) · 4 kW at 380...400 V AC 50/60 Hz (AC-3e) · 4 kW at 415 V AC 50/60 Hz (AC-3e) · 4 kW at 440 V AC 50/60 Hz (AC-3e) · 5.5 kW at 500 V AC 50/60 Hz (AC-3e) · 5.5 kW at 660...690 V AC 50/60 Hz (AC-3e) · 2.2 kW at 400 V AC 50/60 Hz (AC-4) |
|---|
| Motor power hp | 1 hp at 230/240 V AC 50/60 Hz for 1 phase motors · 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors · 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors · 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors · 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors · 0.33 hp at 115 V AC 50/60 Hz for 1 phase motors |
|---|
| Compatibility code | LC1D |
|---|
| Pole contact composition | 3 NO |
|---|
| Protective cover | With |
|---|
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit · 16 A (at 60 °C) for power circuit |
|---|
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947 · 140 A AC for signalling circuit conforming to IEC 60947-5-1 · 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
|---|
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
|---|
| [Icw] rated short-time withstand current | 105 A 40 °C - 10 s for power circuit · 210 A 40 °C - 1 s for power circuit · 30 A 40 °C - 10 min for power circuit · 61 A 40 °C - 1 min for power circuit · 100 A - 1 s for signalling circuit · 120 A - 500 ms for signalling circuit · 140 A - 100 ms for signalling circuit |
|---|
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1 · 25 A gG at <= 690 V coordination type 1 for power circuit · 20 A gG at <= 690 V coordination type 2 for power circuit |
|---|
| Average impedance | 2.5 mOhm - Ith 16 A 50 Hz for power circuit |
|---|
| Power dissipation per pole | 1.56 W AC-1 · 0.2 W AC-3 · 0.2 W AC-3e |
|---|
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1 · Power circuit: 600 V CSA certified · Power circuit: 600 V UL certified · Signalling circuit: 690 V conforming to IEC 60947-1 · Signalling circuit: 600 V CSA certified · Signalling circuit: 600 V UL certified |
|---|
| Overvoltage category | III |
|---|
| Pollution degree | 3 |
|---|
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
|---|
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 · B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
|---|
| Mechanical durability | 30 Mcycles |
|---|
| Electrical durability | 0.6 Mcycles 25 A AC-1 at Ue <= 440 V · 2 Mcycles 9 A AC-3 at Ue <= 440 V · 2 Mcycles 9 A AC-3e at Ue <= 440 V |
|---|
| Control circuit type | DC low consumption |
|---|
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
|---|
| Control circuit voltage limits | 0.1...0.3 Uc (-40…70 °C):drop-out DC · 0.8...1.25 Uc (-40…60 °C):operational DC · 1...1.25 Uc (60…70 °C):operational DC |
|---|
| Inrush power in W | 2.4 W (at 20 °C) |
|---|
| Hold-in power consumption in W | 2.4 W at 20 °C |
|---|
| Operating time | 77 ±15 % ms closing · 25 ±20 % ms opening |
|---|
| Time constant | 40 ms |
|---|
| Maximum operating rate | 3600 cyc/h at 60 °C |
|---|
| Connections - terminals | Power circuit: spring terminals 1 2.5 mm² - cable stiffness: flexible without cable end · Power circuit: spring terminals 2 2.5 mm² - cable stiffness: flexible without cable end · Control circuit: spring terminals 1 2.5 mm² - cable stiffness: flexible without cable end · Control circuit: spring terminals 2 2.5 mm² - cable stiffness: flexible without cable end |
|---|
| Auxiliary contact composition | 1 NO + 1 NC |
|---|
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1 · type mirror contact 1 NC conforming to IEC 60947-4-1 |
|---|
| Signalling circuit frequency | 25...400 Hz |
|---|
| Minimum switching voltage | 17 V for signalling circuit |
|---|
| Minimum switching current | 5 mA for signalling circuit |
|---|
| Insulation resistance | > 10 MOhm for signalling circuit |
|---|
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact · 1.5 ms on energisation between NC and NO contact |
|---|
| Mounting support | Rail · Plate |
|---|