Technical specifications
| Range | TeSys |
|---|
| Product name | TeSys D |
|---|
| Device short name | LR97 |
|---|
| Product or component type | Electronic overcurrent relay |
|---|
| Relay application | Overload Imax > Isetting · Locked rotor, mechanical jamming I > 3 x Isetting · Sensitivity to phase failure |
|---|
| Product compatibility | LC1D09...D38 |
|---|
| Network type | AC |
|---|
| [Us] rated supply voltage | 100...120 V AC |
|---|
| Thermal protection adjustment range | 1.2…7 A |
|---|
| [Ue] rated operational voltage | 600 V AC 50/60 Hz for power circuit conforming to CSA · 600 V AC 50/60 Hz for power circuit conforming to UL · 690 V AC 50/60 Hz for power circuit conforming to IEC 60947-4-1 |
|---|
| Quantity per set | Set of 10 |
|---|
| Network frequency | 50...60 Hz |
|---|
| Mounting support | Direct on contactor · Rail |
|---|
| Tripping threshold | 1.2...6 A |
|---|
| Surge withstand | 6 kV conforming to IEC 61000-4-5 |
|---|
| Contacts type and composition | 1 C/O |
|---|
| [Ith] conventional free air thermal current | 3 A for control circuit |
|---|
| Protection type | BS fuse 3 A - for control circuit · GB2 circuit breaker 3 A - for control circuit · GG fuse 3 A - for control circuit |
|---|
| Maximum power | 28 W at 110 V DC conforming to IEC 60947 · 28 W at 220 V DC conforming to IEC 60947 · 55 W at 24 V DC conforming to IEC 60947 · 55 W at 48 V DC conforming to IEC 60947 · 140 VA at 48 V AC conforming to IEC 60947 · 360 VA at 110 V AC conforming to IEC 60947 · 360 VA at 220 V AC conforming to IEC 60947 · 70 VA at 24 V AC conforming to IEC 60947 |
|---|
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to CSA · Power circuit: 600 V conforming to UL · Power circuit: 690 V conforming to IEC 60947-4-1 |
|---|
| [Uimp] rated impulse withstand voltage | 6 kV |
|---|
| Phase failure sensitivity | < 3 s |
|---|
| Reset | Automatic reset 120 s fixed · Electrical by interruption of power supply for minimum 0.1 s · Manual reset |
|---|
| Time range | 0.2...10 s - O-time knob · 0.3...10 s - O-time knob · 0.5..30 s - D-time knob |
|---|
| Signalling function | 2 LEDs |
|---|
| Connections - terminals | Control circuit: cable 1 x 1…25 mm²flexible with cable end · Control circuit: cable 1 x 1…25 mm²flexible without cable end · Power circuit: cable 1 x 1…4 mm²flexible with cable end · Power circuit: cable 1 x 1.5…10 mm²flexible without cable end · Power circuit: lug-clamp 1 x 1…4 mm²flexible with cable end · Power circuit: lug-clamp 1 x 1.5…10 mm²flexible without cable end · Control circuit: cable 2 x 1…25 mm²flexible with cable end · Control circuit: cable 2 x 1…25 mm²flexible without cable end · Control circuit: lug-clamp 1 x 1…25 mm²flexible with cable end · Control circuit: lug-clamp 1 x 1…25 mm²flexible without cable end · Control circuit: lug-clamp 2 x 1…25 mm²flexible with cable end · Control circuit: lug-clamp 2 x 1…25 mm²flexible without cable end |
|---|
| Tightening torque | Control circuit: 0.6...1.2 N.m on lug-clamp · Power circuit: 2 N.m on cable |
|---|
| Height | 67.5 mm |
|---|
| Width | 45 mm |
|---|
| Depth | 67.5 mm |
|---|
| Product weight | 0.172 kg |
|---|
| Standards | IEC 60947 · IEC 60255-6 |
|---|
| Product certifications | GOST · UL · CSA |
|---|
| Protective treatment | TH conforming to IEC 60068 |
|---|
| IP degree of protection | IP20 conforming to IEC 60529 |
|---|
| Ambient air temperature for operation | -25…60 °C conforming to IEC 60947-4-1 |
|---|
| Ambient air temperature for storage | -30…80 °C |
|---|
| Operating altitude | 2000 m |
|---|
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
|---|
| Shock resistance | 15 gn 11 ms conforming to IEC 60068-2-7 |
|---|
| Vibration resistance | 4 gn conforming to IEC 60068-2-6 |
|---|
| Dielectric strength | 2 V 50 Hz conforming to IEC 60255-5 |
|---|
| Resistance to electrostatic discharge | 6 kV in indirect mode · 8 kV in air |
|---|
| Resistance to radiated fields | 10 V/m level 3 |
|---|
| Resistance to fast transients | 2 kV |
|---|