| Range | TeSys |
|---|
| Product name | TeSys T |
|---|
| Device short name | LTME |
|---|
| Product or component type | Extension module |
|---|
| Device application | Equipment monitoring and control |
|---|
| Range compatibility | TeSys TeSys T LTMR motor controller |
|---|
| Supply | Via the controller |
|---|
| [Ui] rated insulation voltage | 690 V conforming to EN/IEC 60947-1 · 690 V conforming to CSA C22.2 No 14 · 690 V conforming to UL 508 |
|---|
| [Uimp] rated impulse withstand voltage | 6 kV current or voltage measurement circuit conforming to EN/IEC 60947-4-1 · 0.8 kV supply, inputs and outputs conforming to EN/IEC 60947-4-1 |
|---|
| Logic input number | 4 |
|---|
| Input current | 7 mA |
|---|
| Current state 0 guaranteed | Logic input: < 5 V and <= 15 mA for 5 ms |
|---|
| Current state 1 guaranteed | Logic input: < 15 V and 2...15 mA for 15 ms |
|---|
| maximum output switching frequency | 2 Hz |
|---|
| maximum operating rate | 1800 cyc/h |
|---|
| Contacts type and composition | Without |
|---|
| Metering type | Voltage U21, U32, U13, V1, V2, V3 · Imbalance voltage · Frequency · Calculated active and reactive energy (+/- W.h, +/- VAR.h) · Reactive power Q, Q1, Q2, Q3 · Power factor · Active power P, P1, P2, P3 |
|---|
| Measurement accuracy | 1 % voltage (100...830 V) · 3 % power factor · 5 % active and reactive power |
|---|
| Overvoltage category | III |
|---|
| Connection pitch | 5.08 mm |
|---|
| Connections - terminals | Control circuit: connector 1 cable(s) 0.25…2.5 mm² (24 AWG...14 AWG) flexible with cable end · Control circuit: connector 1 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) flexible without cable end · Control circuit: connector 1 cable(s) 0.25…2.5 mm² (24 AWG...14 AWG) flexible without cable end · Control circuit: connector 1 cable(s) 0.2…2.5 mm² (24 AWG...14 AWG) solid without cable end · Control circuit: connector 2 cable(s) 0.2…1 mm² (24 AWG...14 AWG) flexible with cable end · Control circuit: connector 2 cable(s) 0.2…1.5 mm² (24 AWG...14 AWG) flexible without cable end · Control circuit: connector 2 cable(s) 0.5…1.5 mm² (24 AWG...14 AWG) flexible without cable end · Control circuit: connector 2 cable(s) 0.2…1 mm² (24 AWG...14 AWG) solid without cable end |
|---|
| Tightening torque | Control circuit: 0.5…0.6 N.m flat screwdriver 3 mm |
|---|
| Pollution degree | 3 |
|---|
| Electromagnetic compatibility | Electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 · Fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 · Fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 · Conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 · Control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 · Control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5 · Communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 · Voltage inputs: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 · Voltage inputs: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 |
|---|
| Width | 45 mm |
|---|
| Height | 61 mm |
|---|
| Depth | 120.7 mm |
|---|
| Product weight | 0.21 kg |
|---|
| Compatibility code | LTME |
|---|
| Standards | IEC 60947-4-1 · UL 508 · EN 60947-4-1 · IACS E10 · CSA C22.2 No 14 |
|---|
| Product certifications | UL · NOM · ATEX · BV · CSA · EAC · RINA · LROS (Lloyds register of shipping) · DNV · ABS · GL · KERI · RMRoS · C-Tick · CCC |
|---|
| IP degree of protection | IP20 |
|---|
| Protective treatment | 12 x 24 hour cycles conforming to EN/IEC 60068-2-30 · 48 h conforming to EN/IEC 60070-2-11 · TH conforming to EN/IEC 60068 |
|---|
| Fire resistance | 650 °C conforming to EN/IEC 60695-2-12 · 960 °C conforming to UL 94 |
|---|
| Ambient air temperature for operation | -20…60 °C |
|---|
| Ambient air temperature for storage | -40…80 °C |
|---|
| Operating altitude | <= 2000 m without derating |
|---|
| Mechanical robustness | Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27 · Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 · Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6 |
|---|
| Unit Type of Package 2 | S02 |
|---|
| Number of Units in Package 2 | 20 |
|---|
| Package 2 Height | 15.0 cm |
|---|
| Package 2 Width | 30.0 cm |
|---|
| Package 2 Length | 40.0 cm |
|---|
| Package 2 Weight | 4.251 kg |
|---|
| Warranty (in months) | 18 |
|---|