Schneider Electric Touchscreen Room Controller room controller. Touchscreen Room Controller Roof Top Unit, Heat Pump & Indoor Air Quality: BACnet MSTP, RH sensor, PIR sensor, Black.
Touchscreen Room Controller Roof Top Unit, Heat Pump & Indoor Air Quality: BACnet MSTP, RH sensor, PIR sensor, Black. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| AWG gauge | 22 AWG...18 AWG |
|---|
| Height | 120 mm |
|---|
| Temperature resolution | 0.1 °C |
|---|
| Ambient air temperature for storage | -30…50 °C |
|---|
| Depth | 28 mm |
|---|
| Humidity measurement drift | Less than 1 % yearly |
|---|
| Width | 81 mm |
|---|
| Market segment | Lodging/hotel · Small commercial · Buildings · Healthcare · Non-critical buildings · Office · Residential · School |
|---|
| Device application | Roof top unit · Heat pump · Indoor air quality (IAQ) |
|---|
| Product weight | 340 g |
|---|
| Product or component type | Room controller |
|---|
| Product name | Touchscreen Room Controller |
|---|
| Device short name | TRC6500 |
|---|
| Targeted region | Asia Pacific. · Australia. · Europe · Latin America. · Middle East and Africa. · North America. |
|---|
| Directives | 2014/30/EU - electromagnetic compatibility · 2014/35/EU - low voltage directive · 2014/53/EU - radio equipment directive |
|---|
| Housing colour | Black |
|---|
| Ambient air temperature for operation | 0…50 °C |
|---|
| Network frequency | 60 Hz · 50 Hz |
|---|
| Measurement accuracy | Temperature: +/- 0.5 °C, · Humidity: +/- 5 %, 20...80 % RH (non-condensing) · Humidity: +/- 10 %, 10...20 % (non-condensing) · Humidity: +/- 10 %, 80...90 % (non-condensing) |
|---|
| Communication port protocol | BACnet MS/TP · Modbus RTU |
|---|
| Output current | 1 A relay output · 3 A relay output (inrush) · 0.3 A universal output · 1.5 A universal output (inrush) |
|---|
| Relative humidity | 0…75 % |
|---|
| Temperature setting range | 12…37.5 °C cooling · 4.5…32 °C heating |
|---|
| Sensor type | 10 kOhm T2 NTC thermistor temperature · Space RH sensor humidity · Bulk polymer humidity · PIR |
|---|
| [Us] rated supply voltage | 24 V AC 50/60 Hz +/- 15 % · 24 V DC +/- 15 % |
|---|
| Output voltage | 24 V AC/DC for relay output · 0...10 V AC/DC for voltage output |
|---|
| Input type | 8 x universal input |
|---|
| Standards | EN/IEC 60730-1 · FCC part 15 Subpart B · ICES-003 · ETSI EN 300 328 · ETSI EN 301 489-1:v1.9.2 · FCC part 15 Subpart C · UL 60730-2-9 · ETSI EN 301 489-17:v2.2.1, 2012 |
|---|
| Output type | 5 xrelay output · 4 xuniversal output |
|---|
| Input voltage | 0...10 V |
|---|
| Humidity setting range | 30…95 % |
|---|
| Range | SpaceLogic Touchscreen Room Controller |
|---|
| Economizer | No |
|---|
| Humidity control | Yes |
|---|
| PIR cover | Yes |
|---|
| Scheduling | Yes |
|---|
| Surface finish | Matt |
|---|
| Function available | HVAC control · Available with CO2/RH/T · Brightness sensor · Changes can be made directly over display · Code lock function · Easily configurable · Firmware update by USB · Fan control |
|---|
| Pollution degree | 2 |
|---|
| Unit Type of Package 2 | S02 |
|---|
| Number of Units in Package 2 | 7 |
|---|
| Package 2 Height | 15 cm |
|---|
| Package 2 Width | 30 cm |
|---|
| Package 2 Length | 40 cm |
|---|
| Package 2 Weight | 2.36 kg |
|---|