| Range of product | Altivar Process ATV600 |
|---|
| Product specific application | Process and utilities |
|---|
| Product or component type | Variable speed drive |
|---|
| Variant | Standard version |
|---|
| Device short name | ATV630 |
|---|
| Mounting mode | Wall mount |
|---|
| Communication port protocol | Ethernet · Modbus serial · Modbus TCP |
|---|
| [Us] rated supply voltage | 200...240 V - 15...10 % |
|---|
| Relative symmetric mains voltage tolerance | 10 % |
|---|
| Relative symmetric network frequency tolerance | 5 % |
|---|
| nominal output current | 46.8 A |
|---|
| IP degree of protection | IP21 |
|---|
| Product destination | Asynchronous motors · Synchronous motors |
|---|
| EMC filter | Without EMC filter |
|---|
| Degree of protection | UL type 1 conforming to UL 508C |
|---|
| Type of cooling | Forced convection |
|---|
| Supply frequency | 50...60 Hz - 5...5 % |
|---|
| Motor power kW | 11 kW (normal duty) · 7.5 kW (heavy duty) |
|---|
| Motor power hp | 15 hp normal duty · 10 hp heavy duty |
|---|
| Line current | 39.3 A at 200 V (normal duty) · 32.9 A at 240 V (normal duty) · 27.2 A at 200 V (heavy duty) · 23.1 A at 240 V (heavy duty) |
|---|
| Continuous output current | 46.8 A at 4 kHz for normal duty · 32.7 A at 4 kHz for heavy duty |
|---|
| Speed drive output frequency | 0.1…500 Hz |
|---|
| Safety function | STO (safe torque off) SIL 3 |
|---|
| Option card | Slot A: communication module, Profibus DP V1 · Slot A: communication module, PROFINET · Slot A: communication module, DeviceNet · Slot A: communication module, Modbus TCP/EtherNet/IP · Slot A: communication module, CANopen daisy chain RJ45 · Slot A: communication module, CANopen SUB-D 9 · Slot A: communication module, CANopen screw terminals · Slot A/slot B: digital and analog I/O extension module · Slot A/slot B: output relay extension module · Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link · Communication module, BACnet MS/TP · Communication module, Ethernet Powerlink |
|---|
| Discrete input number | 8 |
|---|
| Discrete input type | DI7, DI8 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) |
|---|
| Discrete input logic | 16 preset speeds |
|---|
| Discrete output number | 0 |
|---|
| Discrete output type | Relay outputs R1A, R1B, R1C 250 V AC 3000 mA · Relay outputs R1A, R1B, R1C 30 V DC 3000 mA · Relay outputs R2A, R2C 250 V AC 5000 mA · Relay outputs R2A, R2C 30 V DC 5000 mA · Relay outputs R3A, R3C 250 V AC 5000 mA · Relay outputs R3A, R3C 30 V DC 5000 mA |
|---|
| Analogue input number | 3 |
|---|
| Analogue input type | AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 31.5 kOhm, resolution 12 bits · AI1, AI2, AI3 software-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 12 bits · AI2 voltage analog input: - 10...10 V DC, impedance: 31.5 kOhm, resolution 12 bits |
|---|
| Analogue output number | 2 |
|---|
| Analogue output type | Software-configurable voltage AQ1, AQ2: 0...10 V DC impedance 470 Ohm, resolution 10 bits · Software-configurable current AQ1, AQ2: 0...20 mA, resolution 10 bits · Software-configurable current DQ-, DQ+: 30 V DC · Software-configurable current DQ-, DQ+: 100 mA |
|---|
| Relay output number | 3 |
|---|
| Relay output type | Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles · Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles · Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles |
|---|
| Maximum switching current | Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC · Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC · Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC · Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC |
|---|
| Minimum switching current | Relay output R1, R2, R3: 5 mA at 24 V DC |
|---|
| Network number of phases | 3 phases |
|---|
| Physical interface | Ethernet · 2-wire RS 485 |
|---|
| Method of access | Slave Modbus TCP |
|---|
| Transmission rate | 10, 100 Mbits · 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps |
|---|
| Transmission frame | RTU |
|---|
| Output voltage | <= power supply voltage |
|---|
| Permissible temporary current boost | 1.1 x In during 60 s (normal duty) · 1.5 x In during 60 s (heavy duty) |
|---|
| Data format | 8 bits, configurable odd, even or no parity |
|---|