Schneider Electric PowerLogic capacitor bank. automatic PowerLogic PFC Capacitor bank, 100kvar 400V 60Hz with incomer CB xxB.
automatic PowerLogic PFC Capacitor bank, 100kvar 400V 60Hz with incomer CB xxB. Genuine Schneider Electric product supplied by United Force.
Technical specifications
| Network rated voltage | 400 V AC 60 Hz · 415 V AC 60 Hz |
|---|
| Reactive power rating | 100 kvar |
|---|
| Operating mode | Automatic |
|---|
| Range | PowerLogic |
|---|
| Device short name | automatic capacitor bank |
|---|
| Product or component type | Capacitor bank |
|---|
| Network pollution level | Low polluted |
|---|
| [Gh/Sn] harmonic pollution rate | 15…25 % |
|---|
| [THDU] total harmonic distorsion of voltage | 3…4 % |
|---|
| Power per step | 25 kvar |
|---|
| Step composition | 2x25 + 50 |
|---|
| Location of connection | Bottom |
|---|
| Controller type | PowerLogic PFC Controller VPL6 |
|---|
| capacitor technology | PowerLogic PFC Capacitor |
|---|
| Poles description | 3P |
|---|
| Capacitance tolerance | - 5 % to 10 % |
|---|
| [Ui] rated insulation voltage | 690 V |
|---|
| [Uimp] rated impulse withstand voltage | 8 kV |
|---|
| Maximum permissible voltage | 1.1 x Un (8 hours over 24 hours) conforming to IEC 60831 |
|---|
| [Imp] maximum permanent current | Capacitor: 1.8 x In at 480 V conforming to IEC 60831 · Battery: 1.43 x In at 400 V conforming to IEC 61439-2 · Battery: 1.19 x In at 415 V conforming to IEC 61439-2 |
|---|
| main incomer protection | Circuit breaker protection |
|---|
| Breaking capacity | Icu 50 kA |
|---|
| Control type | Rotary handle |
|---|
| Step protection type | Overload: harmonic control from PowerLogic PFC Controller · Short-circuit: main circuit breaker |
|---|
| Accessibility for operation | Front |
|---|
| Colour | Grey (RAL 7035) |
|---|
| maximum weight | 131 kg |
|---|
| Height | 1300 mm |
|---|
| Width | 800 mm |
|---|
| Depth | 300 mm |
|---|
| Provided equipment | Auxiliary transformer |
|---|
| Internal voltage transformer | 400/230 V - 250 VA |
|---|
| Function available | Alarm contact · GenSet shedding contact |
|---|
| Standards | IEC 61439-2 · IEC 61439-1 · IEC 61921 |
|---|
| Product certifications | CE · ASEFA · EAC |
|---|
| Mounting location | Indoor |
|---|
| IP degree of protection | Environment: IP31 · Safety: IPxx B |
|---|
| IK degree of protection | IK10 |
|---|
| Relative humidity | 0…95 % |
|---|
| Operating altitude | <= 2000 m |
|---|
| Ambient air temperature for operation | -5…45 °C |
|---|
| Average ambient air temperature for operation | 35 °C (annual) · 45 °C (over 24 hours) |
|---|
| Warranty (in months) | 18 |
|---|